2018-06-14 16:58:1906/14/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) THE ISOMETRIC DRAWING IS SHOWING ALL FLAT DRY VENTS.
 ALL HORIZONTAL VENTING SHALL BE WET VENTING COMPLYING
 WITH FBC R P3108 OR A COMBINATION WASTE AND VENT SYSTEM
 COMPLYING WITH FBC R P3111
  
 2) STUDOR VENTS ARE NOT PERMITTED TO BE USED ON A
 WASHING MACHING WHEN THE HORIZONTAL DRAIN IS LESS THEN
 3". FBC R P2609.2
  
 3) SHOW THE REQUIRED CLEAN OUTSIDE WHERE THE BUILDING
 DRAIN AND SEWER CONNECT. FBC R P3005.2.3
  
 6) UNDER SCOPE OF WORK #6 (ADD GAS TANKLESS) PROVIDE
 MANUFACTURE INSTALLATION MANUAL.
  
 7) SEE GAS NOTES. A SUB GAS PERMIT IS REQUIRED FBC
 105.1
  
 8) THE TOTAL JOB VALUE SEEMS LOW. PROVIDE A BONA FIDE
 SIGNED CONTRACT FBC 109.3
  