| 2020-03-11 13:24:16 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. |
| | ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | |
| | 1. CORRECTED. SITE SPECIFIC ENGINEERING PROVIDED. |
| | 2. PROVIDE CITY OF WPB SCHEDULE FOR INSTALLATION OF |
| | OPENING PROTECTIVE DEVICES. (A COPY OF THE SHUTTER |
| | SCHEDULE WILL BE E-MAILED TO APPLICANT) |
| | 3. PROVIDE FLOOR PLAN. IDENTIFY LOCATION OF OPENING TO |
| | BE PROTECTED. (OPENINGS ON FLOOR PLAN SHALL CORRESPOND |
| | TO SHUTTER SCHEDULE) |
| | 4. DESIGNER TO PRINT NAME AND SIGN PLAN. (STILL OPEN) |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE SHUTTER SUBMITTALS. |
| | |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5) AND F.S. 481.229. |
| | |
| | |