Plan Review Notes
Plan Review Notes For Permit 18011102
Permit Number 18011102
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-09 08:26:521ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING
 PERMIT #18011102
 2/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DESIGN CRITERIA: THE FLORIDA BUILDING CODE SIXTH
 EDITION-2017 WENT INTO EFFECT ON JAN.1, 2017. THIS
 PERMIT APPLICATION AND PLANS WERE SUBMITTED AFTER THAT
 DATE. PLEASE UPDATE THE DESIGN PARAMETERS FOR THE
 PROJECT, AND THE DESIGN CRITERIA LISTED ON SHEET A1 TO
 BE IN COMPLIANCE WITH THE CURRENT CODES.
  
 2) THE PROPOSED PROJECT IS CLASSIFIED AS A CHANGE OF
 OCCUPANCY IN ACCORDANCE WITH SECTION 202 FBC-17
 EXISTING BUILDING CODE. COMPLIANCE WITH THE FLORIDA
 ENERGY CONSERVATION- 2017 PER SECTION R505.2 IS
 REQUIRED. PLEASE SEE SECTION R101.5.1.1 AND SUBMIT A
 COMPLIANCE REPORT.
  
 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN COMPLIANCE WITH SECTION C403.2.1 FBC-17
 ENERGY CONSERVATION.
  
 4) MINIMUM VENTILATION FOR THE APARTMENTS, EITHER
 NATURALLY OR MECHANICALLY, IS REQUIRED PER SECTION
 401.2 FBC-17 INDICATE HOW THE APARTMENTS ARE BEING
 VENTILATED- BY NATURAL OR MECHANICAL MEANS, AND PROVIDE
 CALCULATIONS- SEE SECTION 402.2 AND TABLE 403.1.1.
 PLEASE NOTE THAT OUTSIDE AIR DUCTS MUST BE PROTECTED AT
 THE INTAKE LOCATIONS ON THE EXTERIOR OF THE BUILDING
 PER SECTION
  
 401.5, AND THE AIRFLOW THROUGH THE DUCT MUST BE
 CONTROLLED AUTOMATICALLY BY MEANS OF EITHER A MOTORIZED
 OR GRAVITY DAMPER- SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION.
  
 5) SHEET HVAC-1: PROVIDE AC EQUIPMENT SCHEDULES ON THE
 PLAN.
  
 6) PROVIDE STRUCTURAL DETAILS FOR THE NEW CONDENSER
 PADS, AND TIE-DOWN ENGINEERING FOR ANCHORING THE
 CONDENSERS TO THE PADS- SECTION 301.15.
  
 PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR PENDING
 RESUBMITTAL OF CORRECTED PLANS AND DOCUMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  