| 2018-01-31 11:06:37 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18011102 / HISTORIC BUILDING |
| | ADD: 809 6TH ST. |
| | CONT: TBD / TO BE DETERMINED |
| | TEL: 786-290-1268 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 31/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE COVERSHEET A-1 INDICATES THIS IS A |
| | LEVEL III ALTERATION. THE LAST KNOWN USE |
| | (OCCUPANCY R-3) FOR THIS BUILDING WAS A PERMIT 9700268 |
| | MISCELLANEOUS FLOOR REPAIRS AN OWNER/ BUILDER PERMIT. |
| | THIS MADE THE OCCUPANCY TYPE A R3 SINGLE FAMILY |
| | RESIDENCE. THE OWNER BROUGHT IN THEIR HOMESTEAD TAX |
| | EXEMPTION AS PART OF THEIR PROOF OF OWNERSHIP. IN 2014 |
| | ANOTHER PERMIT WAS APPLIED FOR 14120093 TO CHANGE THE |
| | OCCUPANCY CLASSIFICATION FROM A R3 SINGLE FAMILY |
| | DWELLING TO AN R2 A 4 UNIT APARTMENT BUILDING. THIS |
| | PERMIT HAS NEVER BEEN ISSUED AND WAS REVOKED. 4/21/2017 |
| | THE OWNER AND CONTRACTOR WERE ADVISED TO RE-APPLY FOR |
| | THE PERMIT THAT HAD NEVER BEEN ISSUED. REVOKED |
| | 9/15/2017. |
| | |
| | THIS IS A CHANGE OF USE PERMIT UNDER THE 2018 |
| | FBC-EXISTING BUILDING CODE. 1001.2.1 CHANGE OF USE. |
| | ANY WORK UNDERTAKEN IN CONNECTION WITH A CHANGE IN USE |
| | THAT DOES NOT INVOLVE A CHANGE OF OCCUPANCY |
| | CLASSIFICATION OR A CHANGE TO ANOTHER GROUP WITHIN AN |
| | OCCUPANCY CLASSIFICATION SHALL CONFORM TO THE |
| | APPLICABLE REQUIREMENTS FOR THE WORK AS CLASSIFIED IN |
| | CHAPTER 5 AND TO THE REQUIREMENTS OF SECTIONS 1002 |
| | THROUGH 1011. |
| | EXCEPTION: AS MODIFIED IN SECTION 1205 FOR HISTORIC |
| | BUILDINGS. |
| | |
| | 2) PLEASE REVIEW SECTION 1003.1 OF THE 2017 EXIST. |
| | BUILDING CODE. BUILDING ELEMENTS AND MATERIALS IN |
| | PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH SECTION 1012. |
| | |
| | EXISTING BUILDING CODE1012.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 1012.2.1 AND 1012.2.2. |
| | |
| | 2A) 2017 EXISTING BUILDING CODE. 1012.2.1 FIRE |
| | SPRINKLER SYSTEM. WHERE A CHANGE IN OCCUPANCY |
| | CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF |
| | OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT |
| | FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER |
| | 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES |
| | AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED |
| | ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF |
| | THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS. |
| | |
| | 2017 FBC-B [F]903.2.8 GROUP R. AN AUTOMATIC SPRINKLER |
| | SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL |
| | BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R |
| | FIRE AREA. F]903.3 INSTALLATION REQUIREMENTS. AUTOMATIC |
| | SPRINKLER SYSTEMS SHALL BE DESIGNED AND INSTALLED IN |
| | ACCORDANCE WITH SECTIONS 903.3.1 THROUGH 903.3.8. |
| | |
| | 2017 FBC-B F]903.3.1.2 NFPA 13R SPRINKLER SYSTEMS. |
| | AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP |
| | TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS |
| | NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE |
| | PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN |
| | ACCORDANCE WITH NFPA 13R. |
| | 2B 2017 EXISTING BUILDING CODE SECTION 1012.2.2 FIRE |
| | ALARM AND DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY |
| | CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF |
| | OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT |
| | FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER |
| | 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES |
| | A FIRE ALARM AND DETECTION SYSTEM TO BE PROVIDED BASED |
| | ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF |
| | THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS. |
| | 907.2.9 GROUP R-2. FIRE ALARM SYSTEMS AND SMOKE ALARMS |
| | SHALL BE INSTALLED IN GROUP R-2 OCCUPANCIES AS REQUIRED |
| | IN SECTIONS 907.2.9.1 THROUGH 907.2.9.3. |
| | [F]907.2.9.1 MANUAL FIRE ALARM SYSTEM. A MANUAL FIRE |
| | ALARM SYSTEM THAT ACTIVATES THE OCCUPANT NOTIFICATION |
| | SYSTEM IN ACCORDANCE WITH SECTION 907.5 SHALL BE |
| | INSTALLED IN GROUP R-2 OCCUPANCIES WHERE ANY OF THE |
| | FOLLOWING CONDITIONS APPLY: |
| | ANY DWELLING UNIT OR SLEEPING UNIT IS LOCATED MORE THAN |
| | ONE STORY BELOW THE HIGHEST LEVEL OF EXIT DISCHARGE OF |
| | EXITS SERVING THE DWELLING UNIT OR SLEEPING UNIT. |
| | |
| | 3) THE COVERSHEET A1 WILL NEED TO PROVIDE IF TRANSIENT |
| | OR NON-TRANSIENT, THIS WILL AFFECT IF ACCESSIBILITY |
| | BECOMES AN ISSUE, TRANSIENT MAY ALSO BECOME A R-1 |
| | OCCUPANCY CLASSIFICATION. 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 107. 3.5.1.2 MINIMUM PLAN REVIEW |
| | CRITERIA COMMERCIAL BUILDING. 2017 FBC-B 310.1. |
| | 4) THE COVERSHEET - A1 UNDER THE HEADING SCOPE OF WORK |
| | NOTE 5 INDICATES NEW WALL AND CEILING INSULATION. THIS |
| | WILL MEAN THE FIRE BARRIER BETWEEN THE 1ST FLOOR |
| | CEILING AND 2ND FLOOR, FLOOR/ CEILING ASSEMBLY WILL BE |
| | REMOVED. 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. PLEASE REVIEW IN THE |
| | 2017 FBC-B TABLE 707.3.10 FIRE BARRIERS OR HORIZONTAL |
| | ASSEMBLIES BETWEEN FIRE AREAS. RESIDENTIAL HORIZONTAL |
| | FIRE BARRIERS REQUIRES A 2 HOUR. |
| | PLEASE REVIEW IN THE EXIST. BUILD. CODE 1012.5.1.1 FIRE |
| | WALL ALTERNATIVE. WHEN ALL 3 REQUIREMENTS ARE MET A |
| | REDUCTION OF 1 HOUR CAN OCCUR IN THE FLOOR CEILING |
| | ASSEMBLY. SEE EXCEPTION TO BE TAKEN: EXCEPTION: WHERE |
| | HORIZONTAL ASSEMBLIES ARE USED TO LIMIT THE MAXIMUM |
| | ALLOWABLE AREA, THE REQUIRED FIRE RESISTANCE RATING OF |
| | THE HORIZONTAL ASSEMBLIES SHALL BE PERMITTED TO BE |
| | REDUCED BY 1 HOUR PROVIDED THE HEIGHT AND NUMBER OF |
| | STORIES INCREASES ALLOWED FOR AN AUTOMATIC SPRINKLER |
| | SYSTEM BY SECTION 504 OF THE FLORIDA BUILDING CODE, |
| | BUILDING ARE NOT USED FOR THE BUILDINGS. |
| | 5) THE COVERSHEET - A1 UNDER THE HEADING SCOPE OF WORK |
| | NOTES 1,2 & 9 INDICATE THERE WERE TO BE NOA?S SUBMITTED |
| | UNDER THIS REVIEW. THESE PRODUCT APPROVALS WERE TO BE |
| | FOR IMPACT WINDOWS, SOLID EXTERIOR DOORS AND TILE ROOF |
| | SYSTEM. NO PRODUCT WERE SUBMITTED. COMPLY WITH: |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | (B) WINDOWS & MULLIONS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | 7A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | 7B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | 8) THE COVERSHEET - A1 UNDER THE HEADING SCOPE OF WORK |
| | NOTES 6 & 8 BOTH REFER TO SHEET S-1. THIS SHEET IS NOT |
| | INCLUDED IN THE SET OF PLANS NOR IN THE PLAN LEGEND. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. NOTE 6 |
| | INDICATES ON SHEET S-1 THERE ARE TENANT SEPARATION WALL |
| | AND CEILING DETAILS (HORIZONTAL SEPARATION OF FIRE |
| | AREAS). |
| | 8A) COMPLIANCE WITH FBC-B TABLE 707.3.10. / FBC-B 420.3 |
| | HORIZONTAL SEPARATION. FLOOR ASSEMBLIES SEPARATING |
| | DWELLING UNITS IN THE SAME BUILDINGS, FLOOR ASSEMBLIES |
| | SEPARATING SLEEPING UNITS IN THE SAME BUILDING AND |
| | FLOOR ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS |
| | FROM OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME |
| | BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES |
| | IN ACCORDANCE WITH SECTION 711. SHEET D-1 HAS A DETAIL |
| | INDICATING A HORIZONTAL FIRE BARRIER AND LISTING UL L |
| | 501 AS THE 1 HOUR ASSEMBLY. PLEASE PUT THE UL LISTING |
| | IN THE PLANS SINCE THE FIELD INSPECTOR WILL NOT HAVE A |
| | UL LISTING BOOK. |
| | THE UL LISTING L501 HAS MANY SYSTEM ASSEMBLIES FOR |
| | VARIOUS COMPONENTS, IDENTIFY WHICH IS APPLICABLE FOR |
| | THIS PROJECT. |
| | |
| | 8B) PLEASE PROVIDE COMPLIANCE WITH ONE OF THE METHODS |
| | BELOW: EITHER EXTEND THE TENANT SEPARATION WALL INTO |
| | THE CRAWL SPACE WITH FOUNDATION WITH A 1 HOUR FIRE |
| | RATING OR CREATE A 1 HOUR FLOOR/ CEILING ASSEMBLY FOR |
| | THE 1ST FLOOR ASSEMBLY. PROVIDE A ONE HOUR FIRE RATED |
| | ASSEMBLY. FBC-B 708.4 EXCEPTION 1. |
| | 8C) 420.2 SEPARATION WALLS. WALLS SEPARATING DWELLING |
| | UNITS IN THE SAME BUILDING, WALLS SEPARATING SLEEPING |
| | UNITS IN THE SAME BUILDING AND WALLS SEPARATING |
| | DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES |
| | CONTIGUOUS TO THEM IN THE SAME BUILDING SHALL BE |
| | CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH |
| | SECTION 708. SHEET D-1 SHOWS HAS A DETAIL WITH A ONE |
| | HOUR RATING AND LISTING U305, PLEASE PUT THE UL LISTING |
| | IN THE PLANS SINCE THE FIELD INSPECTOR WILL NOT HAVE A |
| | UL LISTING BOOK. |
| | 8D) THE COVERSHEET - A1 HAS A NOTE ON ALL EXTERIOR |
| | DOORS THAT LEAD TO A 2ND STORY STAIRWELL, ONE HOUR |
| | RATED PER NOA. NOA STANDS FOR NOTICE OF ACCEPTANCE, A |
| | MIAMI-DADE PRODUCT APPROVAL REPORT WHERE PRODUCTS WERE |
| | TESTED FOR WIND, WATER INFILTRATION, SMALL AND LARGE |
| | MISSILE RESISTANCE IMPACT TESTING. MIAMI-DADE DOES NOT |
| | TEST FOR FIRE RESISTANCE, A SEPARATE FIRE TESTING |
| | REPORT WILL BE REQUIRED ALONG WITH THE MIAMI-DADE NOA. |
| | CLARIFICATION, 107.2.1.3 FBC- B 716.5./ TABLE 716.5. |
| | FIRE DOOR ASSEMBLIES AND SHUTTERS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND NFPA |
| | 80. |
| | 8E) THE COVERSHEET - A1 THE ENTRY DOOR INTO UNIT # 1 IS |
| | NOT A FIRE RATED DOOR. PLEASE NOTE THIS DOOR SHOULD NOT |
| | BE LOCATED IN THE STAIRWELL. THE ENTRY DOOR INTO UNIT # |
| | 1 SHOULD BE ON THE EXTERIOR OF THE BUILDING. THE IDEA |
| | OF HAVING THE TENANT # 1 WITH THEIR DOOR IN THE |
| | VERTICAL EXIT, IF THE DOOR IS LEFT OPEN, OR BLOCKED AND |
| | A FIRE IS IN THAT UNIT, THE SMOKE AND HEAT FROM THE |
| | FIRE WILL MAKE THE STAIRWELL IMPASSABLE. EXIT ACCESS |
| | CORRIDORS ARE TO LEAD INTO THE VERTICAL EXIT. THERE IS |
| | LESS FUEL LOAD IN AN EXIT ACCESS CORRIDOR THAN IN A |
| | HABITUAL SPACE. DEFINITION: EXIT ACCESS. THAT PORTION |
| | OF A MEANS OF EGRESS SYSTEM THAT LEADS FROM ANY |
| | OCCUPIED PORTION OF A BUILDING OR STRUCTURE TO AN EXIT. |
| | 8F) THE COVERSHEET - A1 WILL NEED TO SHOW ONE HOUR FIRE |
| | RATED WALL ON BOTH SIDES OF THE STAIR (INTERIOR WALLS) |
| | ON SHEET A1 AND ON SHEET A2. THE PLANS ARE ALSO SILENT |
| | ON SHEET A1 THE FIRE RATING ON THE CEILING JUST BENEATH |
| | THE STAIR STRINGER. PLEASE REVIEW SECTION: |
| | 2017 FBC-B 1011.7.3 ENCLOSURES UNDER INTERIOR |
| | STAIRWAYS. THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE |
| | SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE |
| | PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION |
| | OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY |
| | ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED |
| | SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIRWAY |
| | ENCLOSURE. |
| | EXCEPTION: SPACES UNDER STAIRWAYS SERVING AND CONTAINED |
| | WITHIN A SINGLE RESIDENTIAL DWELLING UNIT IN GROUP R-2 |
| | OR R-3 SHALL BE PERMITTED TO BE PROTECTED ON THE |
| | ENCLOSED SIDE WITH 1/2-INCH (12.7 MM) GYPSUM BOARD. |
| | |
| | 8G) THE COVERSHEET-A1 INDICATES NEW WINDOWS. SHEET D-1 |
| | INDICATES A WOOD FRAME BUILDING. THE PALM BEACH COUNTY |
| | PROPERTY APPRAISERS OFFICE LIST THE CONSTRUCTION TYPE |
| | AS EXTERIOR WALLS WOOD FRAME STUCCO/ HOLLOW TILE. |
| | PLEASE PROVIDE A DETAIL SHOWING WHERE THE WINDOW IS TO |
| | BE INSTALLED, WITHIN THE HOLLOW CLAY TILE WALL SYSTEM |
| | OR THE WOOD FRAME SYSTEM. IF IN THE HOLLOW CLAY TILE |
| | THE PRODUCT APPROVALS WERE NEVER TESTED THAT WAY. IF IN |
| | THE WOOD FRAME SYSTEM, SHOW HOW THE GAP BETWEEN THE |
| | HOLLOW CLAY TILE AND WOOD FRAMING IS MADE WEATHER |
| | TIGHT. |
| | |
| | 2017 FBC-B 1405.13 EXTERIOR WINDOWS AND DOORS. WINDOWS |
| | AND DOORS INSTALLED IN EXTERIOR WALLS SHALL CONFORM TO |
| | THE TESTING AND PERFORMANCE REQUIREMENTS OF SECTION |
| | 1709.5. |
| | |
| | |
| | 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 8H) SHEET A1 & A2 BOTH INDICATE THE USE OF A 25 SINGLE |
| | HUNG WINDOW. PLEASE PROVIDE FROM THE MANUFACTURER THE |
| | SIZE OF WINDOW THIS REPRESENTS. THIS SHOULD ALSO MATCH |
| | UP WITH THE SIZING CHARTS ON THE PRODUCT APPROVALS |
| | SUBMITTED FOR WINDOWS. THEY MUST COMPLY WITH THE |
| | REQUIREMENTS FOR EMERGENCY ESCAPE OPENINGS FOR SLEEPING |
| | ROOMS. 2017 FBC-B 1030.2.(1-4). |
| | |
| | 9) THE COVERSHEET - A1 NOTE 10 INDICATES NEW FLOOR BUT |
| | DOES NOT INDICATE WHAT TYPE OF NEW FLOOR COVERING. |
| | PLEASE PROVIDE CODE COMPLIANCE FOR TILE, STONE, MARBLE, |
| | VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 9A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 9B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 9C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2 |
| | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE |
| | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 10) SHEET A-3 THE WIND DESIGN DATA: |
| | 10A) AT THE BOTTOM OF THE WIND DESIGN DATA CHART THE |
| | PLANS INDICATE THE WIND DESIGN IS UNDER THE 2010 FBC-B. |
| | PLEASE NOTE THE 2017 FBC FAMILY OF CODES WAS ADOPTED |
| | STATEWIDE ON DEC. 31/ 2017. PLEASE UPDATE THE PLANS. |
| | |
| | 10 B) THE PRESSURES ARE LOW FOR 132 MPH VASD, EXPOSURE |
| | C AND A MEAN ROOF HEIGHT OF 25 FEET. SEE BELOW: |
| | ZONE 1 7/ 27 DEGREES OFF BY -1.42 PSF LOW |
| | ZONE 2 7/ 27 DEGREES OFF BY -3.00 PSF LOW |
| | ZONE 3 7/ 27 DEGREES OFF BY -3.84 PSF LOW |
| | ZONE 4 INT. WALL ZONE OFF BY -1.94 PSF LOW |
| | ZONE 5 END WALL ZONE OFF BY -2.37 PSF LOW |
| | |
| | 11A) SHEET A-2 THE 2ND FLOOR PLAN DOES NOT HAVE A |
| | CEILING PLAN, PLEASE SHOW COMPLIANCE WITH ATTIC ACCESS. |
| | 2017 FBC-B 1209.2 ATTIC SPACES. AN OPENING NOT LESS |
| | THAN 20 INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE |
| | PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF |
| | OVER 30 INCHES (762 MM). CLEAR HEADROOM OF NOT LESS |
| | THAN 30 INCHES (762 MM) SHALL BE PROVIDED IN THE ATTIC |
| | SPACE AT OR ABOVE THE ACCESS OPENING. |
| | |
| | 11B) 1209.3 MECHANICAL APPLIANCES. ACCESS TO MECHANICAL |
| | APPLIANCES INSTALLED IN UNDER-FLOOR AREAS, IN ATTIC |
| | SPACES AND ON ROOFS OR ELEVATED STRUCTURES SHALL BE IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL. |
| | |
| | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF |
| | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR |
| | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE |
| | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST |
| | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE |
| | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |