Text |
| 2018-02-12 09:32:21 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION #18011081 | | | MASTER #16090832 | | | 2/12/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-222: MISSING FIRE DAMPERS FOR DUCTS | | | PENETRATING THE FIRE-RATED MECHANICAL ROOM/FUTURE | | | EXPANSION AREA WALL- SECTION 607.5.2. | | | | | | 2) SUBMIT TWO COPIES OF THE O/A LOUVER PRODUICT | | | APPROVAL OR NOA WITH APPROVAL STAMP BY THE EOR. | | | | | | 3) INDICATE COMPLIANCE WITH SECTION C403.2.4.4 FBC-14 | | | ENERGY CONSERVATION FOR REQUIRED AUTOMATIC CONTROL OF | | | THE OUTSIDE AIRFLOW TO THE AIR HANDLER. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|