Plan Review Notes
Plan Review Notes For Permit 18011081
Permit Number 18011081
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-12 09:32:211ST REVIEW FBC-2014 MECHANICAL
 REVISION #18011081
 MASTER #16090832
 2/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-222: MISSING FIRE DAMPERS FOR DUCTS
 PENETRATING THE FIRE-RATED MECHANICAL ROOM/FUTURE
 EXPANSION AREA WALL- SECTION 607.5.2.
  
 2) SUBMIT TWO COPIES OF THE O/A LOUVER PRODUICT
 APPROVAL OR NOA WITH APPROVAL STAMP BY THE EOR.
  
 3) INDICATE COMPLIANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION FOR REQUIRED AUTOMATIC CONTROL OF
 THE OUTSIDE AIRFLOW TO THE AIR HANDLER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  