Plan Review Notes
Plan Review Notes For Permit 18011080
Permit Number 18011080
Review Stop B
Sequence Number 2
Notes
Date Text
2018-02-26 18:04:08PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS HAVE SEVERAL REFERENCES
 TO THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION
 (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION
 (2017).
  
 2) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE GENERATOR AND THE
 TRANSFER SWITCH. FBC 107.2.1
  
 3) THE PROJECT IS LOCATED IN FLOOD ZONE AE, WHICH IS A
 SPECIAL FLOOD HAZARD AREA. THE GENERATOR AND EQUIPMENT
 IS REQUIRED TO BE LOCATED ABOVE THE REQUIRED BASE FLOOD
 ELEVATION.
  