| Plan Review Notes For Permit 18011080 |
| Permit Number |
18011080 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-08 07:35:58 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD DRAWINGS HAVE SEVERAL REFERENCES | | | TO THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION | | | (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW | | | PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED | | | TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION | | | (2017). | | | | | | 2) THE DRAWINGS FOR THE GENERATOR PAD ARE REQUIRED TO | | | BE SIGNED AND SEALED BY A FLORIDA LICENSED ENGINEER. | | | FBC 107.1 | | | | | | 3) THE AMERICAST GENERATOR PAD DRAWINGS THAT WERE | | | SUBMITTED ARE FROM AN ENGINEER WITH A LICENSE THAT HAS | | | BEEN REVOKED. RONALD H. WILSON'S FLORIDA PE LICENSE WAS | | | REVOKED ON 2/28/2017. | | | | | | 4) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS | | | AND INSTALLATION INSTRUCTIONS FOR THE GENERATOR AND THE | | | TRANSFER SWITCH. FBC 107.2.1 | | | | | | 5) THE PROJECT IS LOCATED IN FLOOD ZONE AE, WHICH IS A | | | SPECIAL FLOOD HAZARD AREA. THE GENERATOR AND EQUIPMENT | | | IS REQUIRED TO BE LOCATED ABOVE THE REQUIRED BASE FLOOD | | | ELEVATION. | | | |
|