| 2018-01-30 06:17:23 | 2014 FBC- BUILDING PLAN REVIEW |
| | W.P.B. REVISION 18011074 |
| | W. P. B. PERMIT: 17040694 |
| | ADD: 3000 N. AUSTRALIAN AVE. |
| | CONT: DOSDOURIAN ENTERPRISES |
| | TEL: 561-644-4704 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 30/ 2018 |
| | ACTION: PASSED |
| | |
| | 804.4.1 TEST REQUIREMENT. |
| | IN ALL OCCUPANCIES, INTERIOR FLOOR COVERING MATERIALS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE DOC FF-1 |
| | ?PILL TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D |
| | 2859. |
| | |
| | 804.4.2 MINIMUM CRITICAL RADIANT FLUX. |
| | IN ALL OCCUPANCIES, INTERIOR FLOOR FINISH AND FLOOR |
| | COVERING MATERIALS IN ENCLOSURES FOR STAIRWAYS AND |
| | RAMPS, EXIT PASSAGEWAYS, CORRIDORS AND ROOMS OR SPACES |
| | NOT SEPARATED FROM CORRIDORS BY PARTITIONS EXTENDING |
| | FROM THE FLOOR TO THE UNDERSIDE OF THE CEILING SHALL |
| | WITHSTAND A MINIMUM CRITICAL RADIANT FLUX. THE MINIMUM |
| | CRITICAL RADIANT FLUX SHALL NOT BE LESS THAN CLASS I IN |
| | GROUPS I-1, I-2 AND I-3 AND NOT LESS THAN CLASS II IN |
| | GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S. |
| | |
| | EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE |
| | PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE |
| | REQUIRED, AND MATERIALS COMPLYING WITH DOC FF-1 ?PILL |
| | TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D 2859 ARE |
| | PERMITTED IN ANY AREA WHERE CLASS II MATERIALS ARE |
| | REQUIRED. |
| | |
| | PRODUCT: PATCRAFT |
| | COLLECTION: SPEAK YOUR LANGUAGE |
| | STYLE 10239 |
| | PRODUCT TYPE MODULAR CONSTRUCTION MULTI-LEVEL PATTERN |
| | LOOP |
| | FIBER STYLE: ECO SOLUTION Q NYLON |
| | METHANAMINE PILL TEST PASSES (DOCFF-1-70) RADIANT PANEL |
| | CLASS I |
| | |
| | 804.4.2 MINIMUM CRITICAL RADIANT FLUX. |
| | IN ALL OCCUPANCIES, INTERIOR FLOOR FINISH AND FLOOR |
| | COVERING MATERIALS IN ENCLOSURES FOR STAIRWAYS AND |
| | RAMPS, EXIT PASSAGEWAYS, CORRIDORS AND ROOMS OR SPACES |
| | NOT SEPARATED FROM CORRIDORS BY PARTITIONS EXTENDING |
| | FROM THE FLOOR TO THE UNDERSIDE OF THE CEILING SHALL |
| | WITHSTAND A MINIMUM CRITICAL RADIANT FLUX. THE MINIMUM |
| | CRITICAL RADIANT FLUX SHALL NOT BE LESS THAN CLASS I IN |
| | GROUPS I-1, I-2 AND I-3 AND NOT LESS THAN CLASS II IN |
| | GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S. |
| | |
| | EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE |
| | PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE |
| | REQUIRED, AND MATERIALS COMPLYING WITH DOC FF-1 ?PILL |
| | TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D 2859 ARE |
| | PERMITTED IN ANY AREA WHERE CLASS II MATERIALS ARE |
| | REQUIRED. |
| | |
| | |
| | |