| Plan Review Notes For Permit 18011037 |
| Permit Number |
18011037 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-02-13 19:06:36 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD PLANS HAVE SEVERAL REFERENCES TO | | | THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION | | | (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW | | | PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED | | | TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION | | | (2017). | | | | | | 2) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE | | | FLORIDA LICENSED ENGINEER'S SEAL AND HANDWRITTEN | | | SIGNATURE AFFIXED PER FLORIDA STATUTE 471 AND FAC | | | 61G15-23.003. |
|