| 2018-02-09 15:48:02 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| | PERMITTED. PROVIDE DETAILS OF SERVICE FOR MAIN HOUSE. |
| | PROVIDE CORRECTION AND/OR CLARIFICATION. FBC 107.2.1; |
| | NEC 230.2; FBC RE E3601.2 |
| | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| | E3609.3; FBC 107.2.1 |
| | 3. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| | CIRCUIT. NEC 250.32; FBC RE3607.3 |
| | 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR THE SUB-PANELS IN THE |
| | CARRIAGE HOUSE. NEC 225.31, 225.32 |
| | 5. BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC |
| | 210.12; FBC RE E3902.16 |
| | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 7. GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN |
| | GARAGE, INCLUDING THE GARAGE DOOR OPENER. PROVIDE |
| | CORRECTION. NEC 210.8; FBC RE E3902.2 |
| | 8. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 9. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. INCLUDE ALL LOADS, CURRENTLY THE WASHERS |
| | AND DRYERS ARE NOT INCLUDED. NEC 215.2, 220, 408.30; |
| | FBC RE E3602.2 |
| | 10. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR |
| | ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| | CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| | TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; |
| | FBC RE E3706.2, E3902 |
| | 11. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 12. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |