| Plan Review Notes For Permit 18011030 |
| Permit Number |
18011030 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-10 18:31:53 | 04/10/2018 PLUMBING 2ND REVIEW**DENIED** | | | | | | 1) YOU HAVE ADDED THE WASHING MACHINE TO THE PLUMBING | | | ISOMETRIC DRAWING BUT IT IS CONNECTED INTO THE | | | HORIZONTAL WET VENT OF THE BATHROOM GROUP WHICH IS NOT | | | PERMITTED PER FBC-R P3108.1. IT MUST CONNECT DOWN | | | STREAM OF THE BATHRROM GOUP ALONG WITH THE BAR SINK. | | | | | | 2) PER THE STUDOR VENT MANUFACTURE INSTALLATION MANUAL | | | YOU MUST RUN 3" TO THE WASHING MACHINE ON THE | | | HORIZONTAL RUN LEADING UP TO IT. FBC-R P 3114.2 | | | | | | 3) SHOW ALL PIPE SIZING ON THE ISOMETRIC DRAWING. FBC | | | 107.2.1 | | | | | | 4) PROVIDE TANKLESS WATER HEATER SPEC/ FULL | | | INSTALLATION MANUAL. | | | | | | 5) YOUR PLAN IS SHOWING A GAS TANKLESS WATER HEATER AND | | | GENERATOR BUT NO GAS APPLICATION OR PLAN HAS BEEN | | | PROVIDED. | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|