Plan Review Notes
Plan Review Notes For Permit 18011030
Permit Number 18011030
Review Stop P
Sequence Number 2
Notes
Date Text
2018-04-10 18:31:5304/10/2018 PLUMBING 2ND REVIEW**DENIED**
  
 1) YOU HAVE ADDED THE WASHING MACHINE TO THE PLUMBING
 ISOMETRIC DRAWING BUT IT IS CONNECTED INTO THE
 HORIZONTAL WET VENT OF THE BATHROOM GROUP WHICH IS NOT
 PERMITTED PER FBC-R P3108.1. IT MUST CONNECT DOWN
 STREAM OF THE BATHRROM GOUP ALONG WITH THE BAR SINK.
  
 2) PER THE STUDOR VENT MANUFACTURE INSTALLATION MANUAL
 YOU MUST RUN 3" TO THE WASHING MACHINE ON THE
 HORIZONTAL RUN LEADING UP TO IT. FBC-R P 3114.2
  
 3) SHOW ALL PIPE SIZING ON THE ISOMETRIC DRAWING. FBC
 107.2.1
  
 4) PROVIDE TANKLESS WATER HEATER SPEC/ FULL
 INSTALLATION MANUAL.
  
 5) YOUR PLAN IS SHOWING A GAS TANKLESS WATER HEATER AND
 GENERATOR BUT NO GAS APPLICATION OR PLAN HAS BEEN
 PROVIDED.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  