| 2018-05-23 11:15:28 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. PROVIDE 2 COPY'S OF THE GAS PLAN THAT ARE PRINTED IN |
| | INK ONE OF THE COPY'S YOU PROVIDED WAS IN PENCIL DOES |
| | NOT COMPLY IT ALSO SHALL BE SIGNED BY THE QUALIFIER OF |
| | QUEENS PLUMBING. PER WPB AMEND TO FBC 107.2.1, |
| | 107.2.1.3 |
| | |
| | 2. PROVIDE ON THE RISER THE BTU LOAD OF EACH GAS |
| | APPLIANCE EXISTING AND NEW. PER FBC-2017 FUEL GAS SECS. |
| | 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). |
| | |
| | 3. PLEASE SHOW ON THE GAS RISER THE FOLLOWING |
| | A) THE LENGTH OF EACH CUT SECTION OF PIPE NEW OR |
| | EXISTING. |
| | B) THE SIZE AND TYPE OF PIPE. |
| | C) ANY VALES AND REGULATORS AND DRIP LEGS. |
| | D) THE SYSTEM PRESSURE. |
| | E) TYPE OF GAS. |
| | PER FBC-2017 FUEL GAS SECS. 401.8 THRU 402.6.1 AND |
| | TABLES 402.4(1) THRU 402.4(37). AND WPB AMEND TO FBC |
| | 107.2.1, 107.2.1.3 |
| | |
| | 4. PROVIDE FLOOR PLAN SHOWING LOCATION OF ALL GAS |
| | APPLIANCES. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. PLEASE PROVIDE THE SIZING TABLE THAT WAS USED IN |
| | SIZING SYSTEM FROM FBC FG 402.4 |
| | |
| | 6. PROVIDE LONGEST LENGTH FROM METER OR SOURCE OF GAS |
| | TO FURTHEST APPLIANCE. PER THE FBC-2014 FUEL GAS |
| | APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4) & 2017 |
| | FUEL GAS CODE SEC. 402.4.1. |
| | |
| | 7. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATIONS |
| | GUIDES FOR ALL NEW GAS APPLIANCES AND REGULATORS. THE |
| | SPEC THAT WAS PROVIDED FOR TANKLESS WATER HEATER DID |
| | NOT INCLUDE INSTALLATION GUIDE. TO VERIFY COMPLIANCE |
| | WITH STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS |
| | SEC. 402.2 |
| | |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |