Plan Review Notes
Plan Review Notes For Permit 18011030
Permit Number 18011030
Review Stop P
Sequence Number 1
Notes
Date Text
2018-02-21 17:38:0402/21/2018 PLUMBING 1ST REVIEW**DENIED**
  
 1) WASHING MACHINE ON FLOOR PLAN IS NOT ON PLUMBING
 SANITARY ISOMETRIC. FBC 107.3.5 PLUMBING #13
  
 2) SHUT ACCESS TO SHUT OFF VALVE FOR WASHING MACHINE TO
 COMPLY WITH FBC-R P2903.9.3
  
 3) SHOW LOCATION OF EXISTING KITCHEN SINK THAT YOU
 INTENT ON CONNECTING THE NEW OUTSIDE SINK TO. NOTE. IF
 PIPING IS GOING TO BE RAN OUTSIDE OF BUILDING IT WOULD
 BE ON ITS OWN SYSTEM/ BUILDING DRAIN AND REQUIRED A
 VENT TO EXTENT TO THE OUTDOORS. AN AAV WOULD NOT BE
 PERMITTED.FBC R P3102.1
  
 4) SUBMIT A FLOOR PLAN SHOWING THE DISTANCE TO ANY DOOR
 OR WINDOW THAT OPENINGS FROM THE LOCATION OF THE
 TANKLESS. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  