| Notes |
| Date |
Text |
| 2018-02-21 17:38:04 | 02/21/2018 PLUMBING 1ST REVIEW**DENIED** | | | | | | 1) WASHING MACHINE ON FLOOR PLAN IS NOT ON PLUMBING | | | SANITARY ISOMETRIC. FBC 107.3.5 PLUMBING #13 | | | | | | 2) SHUT ACCESS TO SHUT OFF VALVE FOR WASHING MACHINE TO | | | COMPLY WITH FBC-R P2903.9.3 | | | | | | 3) SHOW LOCATION OF EXISTING KITCHEN SINK THAT YOU | | | INTENT ON CONNECTING THE NEW OUTSIDE SINK TO. NOTE. IF | | | PIPING IS GOING TO BE RAN OUTSIDE OF BUILDING IT WOULD | | | BE ON ITS OWN SYSTEM/ BUILDING DRAIN AND REQUIRED A | | | VENT TO EXTENT TO THE OUTDOORS. AN AAV WOULD NOT BE | | | PERMITTED.FBC R P3102.1 | | | | | | 4) SUBMIT A FLOOR PLAN SHOWING THE DISTANCE TO ANY DOOR | | | OR WINDOW THAT OPENINGS FROM THE LOCATION OF THE | | | TANKLESS. FBC 107.2.1 | | | | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | | | | |
|