Plan Review Notes
Plan Review Notes For Permit 18011030
Permit Number 18011030
Review Stop E
Sequence Number 1
Notes
Date Text
2018-02-19 14:40:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODES ABOVE)
 2. PROVIDE PANEL SCHEDULE FOR NEW PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4; FBC RE E3706.2, E3902
 3. PROVIDE RISER DIAGRAM FOR UPGRADED SERVICE MENTIONED
 IN LOAD CALCULATION, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; FBC 107.2.14.
 4. PROVIDE UPDATED STATEMENT FOR AFCI PROTECTION. THE
 2014 NEC REQUIRES: ?BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED.? PROVIDE CORRECTION. NEC 210.12; FBC RE
 E3902.16
 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. BECAUSE THE PANEL
 SCHEDULE WAS NOT PROVIDED, THE REVIEWER WAS NOT ABLE TO
 VERIFY THIS. PROVIDE CORRECTION IF NEEDED. NEC
 210.11(C)(3) , FBC RE E3703.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER