| Plan Review Notes For Permit 18010936 |
| Permit Number |
18010936 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-06-14 18:33:38 | BUILDING REVIEW APPROVED WITH PROVISO (DEFERRED | | | SUBMITTAL): | | | 1- SUBMIT ALL PRODUCT APPROVALS FOR ALL DOORS, WINDOWS, | | | MULLIONS, STOREFRONT, ETC. APPROVED BY THE ARCHITECT OF | | | RECORD. | | | NOTE: ENTRANCE DOOR NOA 17-1114.01 SUBMITTED. CLEARLY | | | SPECIFY DOOR AND GLASS TYPE AS REQUIRED BY THE | | | INSTRUCTIONS ON DRAWING W17-54 SUBMITTED. | | | | | | 2- CLEARLY IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY | | | ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER | | | OF RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED | | | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE | | | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 | | | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN | | | ACCORDANCE WITH APPROVED MANUFACTURER'S INSTRUCTIONS. | | | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH | | | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM | | | LOADS AND SPACING USED IN THE TESTS. |
|