Plan Review Notes
Plan Review Notes For Permit 18010936
Permit Number 18010936
Review Stop B
Sequence Number 3
Notes
Date Text
2018-05-25 15:40:41CHANGE OF OF OCCUPANCY TO INSTITUTIONAL I-1 (CONDITION
 1) , THIRD BUILDING REVIEW CHECKLIST
 CODE: FBC 6TH EDITION (2017).
  
 1- ORIGINAL COMMENT:
 THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 209.3 MEDICAL CARE AND LONG-TERM
 CARE FACILITIES. AT LEAST ONE PASSENGER LOADING ZONE
 COMPLYING WITH 503 SHALL BE PROVIDED AT AN ACCESSIBLE
 ENTRANCE TO LICENSED MEDICAL CARE AND LICENSED
 LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY
 EXCEEDS TWENTY-FOUR HOURS.
  
 RESPONSE:
 REPEAT COMMENT. PARTIALLY ADDRESSED. PASSENGER LOADING
 ZONE LOCATION WAS REVISED ON THE PLOT PLAN BUT NEEDS TO
 COMPLY WITH THE LENGTH (SEC. 503.3.2), MARKING (SEC.
 503.3.3) AND FLOOR AND GROUND SURFACES. HANDICAP RAMP
 DETAIL PROVIDED ON SHEET P-1 DOESN'T APPLY TO THE FLOOR
 AND GROUND SURFACE SEC. 503.4. REVISE AS REQUIRED.
  
 2- ORIGINAL COMMENT:
 UNISEX RESTROOM AND ADJACENT BATHROOM DON'T COMPLY WITH
 THE OVERLAP REQUIREMENTS OF SEC. 604.3.2
 FBC-ACCESSIBILITY.
 AND WITH RESTROOM FIXTURE CLEARANCE DETAIL SHOWN ON
 SHEET A-5. REVISE AS REQUIRED.
 (NOTE: SHOWER IS NOT DRAWN TO SCALE IN THIS ROOM. ALSO,
 SOME ROOMS AND CORRIDORS ARE NOT DRAWN TO THE SPECIFIED
 DIMENSIONS. PLEASE VERIFY THAT ALL SPECIFIED DIMENSIONS
 WILL BE PROVIDED IN FIELD TO AVOID CONFLICTS/DELAYS).
  
 RESPONSE:
 REPEAT COMMENT. THE LAVATORY REVISED POSITION DOESN'T
 ALLOW A FORWARD APPROACH AS REQUIRED BY SEC. 606.2
 FBC-ACCESSIBILITY. ALSO, UNISEX RESTROOM AND ADJACENT
 BATHROOM DON'T COMPLY WITH THE OVERLAP REQUIREMENTS OF
 SEC. 604.3.2 FBC-ACCESSIBILITY AND WITH RESTROOM
 FIXTURE CLEARANCE DETAIL SHOWN ON SHEET A-5. REVISE AS
 REQUIRED. THE DOTTED LINE SHOWING THE WATER CLOSET AND
 LAVATORY CLEARANCE ARE NOT DRAWN TO SCALE. BESIDES,
 SHEET A-2 DOESN'T PROVIDE THE DIMENSIONS FOR THESE
 ROOMS. THEREFORE, I AM UNABLE TO VERIFY COMPLIANCE.
 SCALING DRAWINGS IS NOT ALLOWED. WRITTEN DIMENSIONS
 TAKE PRECEDENCE. REVISE PLANS AS REQUIRED.
 NOTE: THERE ARE MANY AREAS IN THESE DRAWINGS THAT ARE
 NOT DRAWN TO SCALE AND DON'T REFLECT THE GIVEN
 DIMENSION. FOR EXAMPLE NOT ALL CORRIDORS MEASURE 60" AS
 SPECIFIED ON SHEET A-4. THESE WAS NOTED ON PREVIOUS
 COMMENT.
 SPECIFY THE SIZE OF EXISTING DOOR #3. TO VERIFY
 COMPLIANCE WITHOUT EH MINIMUM CLEAR WIDTH OPENING.
 ALSO, CLARIFY WHY DOOR HARDWARE FOR THESE TWO BATHROOMS
 IS DIFFERENT THAN THE OTHER BATHROOMS. CLEARLY SPECIFY
 THE DOOR HARDWARE FOR ALL DOORS TO VERIFY COMPLIANCE
 WITH SEC. 309 FBC-ACCESSIBLE.
  
 3- ORIGINAL COMMENT:
 THE DESIGN PRESSURES SHOWN ARE TOO LOW BASED ON THE
 MEAN ROOF HEIGHT SPECIFIED (30'). REVISE AS REQUIRED.
 AND, CLEARLY INDICATE THAT DESIGN PRESSURES ARE NOMINAL
 DESIGN PRESSURES (VASD).
  
 RESPONSE:
 REPEAT COMMENT. PARTIALLY ADDRESSED. REVISED DESIGN
 PRESSURES SHOWN ON SHEET A-4 ARE INCORRECT AND ARE NOT
 CLEAR. CLARIFY WHY SPECIFYING TWO DIFFERENT MEAN ROOF
 HEIGHTS. THE ADJUSTMENT FACTOR FOR A MEAN ROOF HEIGHT
 OF 20' ' IS 1.29 NOT 1.21. AND THE ADJUSTMENT FACTOR
 FOR A MEAN ROOF HEIGHT OF 24' IS 1.35 NOT 1.21. REVISE
 AS REQUIRED. SEE TABLE 1609.7(2) FBC.
  
 4- WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 5- ORIGINAL COMMENT:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 RESPONSE:
 A) ENTRANCE DOOR NOA 17-1114.01 SUBMITTED. CLEARLY
 SPECIFY DOOR AND GLASS TYPE AS REQUIRED BY THE
 INSTRUCTIONS ON DRAWING W17-54 SUBMITTED.
 NOTE: PRODUCT APPROVAL MAY BE SUBMITTED LATER AS
 "DEFERRED SUBMITTAL" AFTER THE PERMIT IS ISSUED, BUT
 BEFORE ANY INSPECTIONS TO AVOID CONFLICT DELAYS.
  
 6- ORIGINAL COMMENT:
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- ORIGINAL COMMENT:
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 8- BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 9- PLEASE NOTE A THOROUGH REVIEW COULD NOT BE COMPLETED
 IN THIS REVIEW AND DEPENDING ON THE RESPONSE COMMENTS
 ADDITIONAL COMMENTS MAY OCCUR ON THE FOLLOWING REVIEWS.
 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 10- WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 NEW COMMENTS:
  
 11- SLEEPING ROOMS NEED TO HAVE SEPARATION WALLS WITH
 FIRE PARTITIONS AS REQUIRED BY SEC. 420..2 FBC.
 IDENTIFY WALL IN PLANS AND PROVIDE FIRE RATED WALL
 DETAIL AND SPECIFICATIONS.
 NOTE: I APOLOGIZE. IT WAS OVERLOOKED ON PREVIOUS
 REVIEW. I TAUGHT THEY WERE SPECIFIED AS FIRE RATED
 WALLS.
  
 12- PARKING CALCULATIONS INFORMATION ON SHEET P-1 NEEDS
 TO BE REVISED TO REFLECT THE ACTUAL NUMBER OF PARKING
 SPACES SHOWN ON-THE REVISED PLOT PLAN. SEC. 107.2.1
 CITY AMENDMENTS.
  
 13-CLARIFICATION: MINIMUM REQUIRED CORRIDOR WIDTH IS
 44" NOT 42". TABLE 1020.2 FBC. REVISE INFORMATION ON
 SHEET A-4 AS REQUIRED.
  
 14- THE FENCED YARD NEEDS TO BE ACCESSIBLE. SEC.
 206.2.2 FBC ACCESSIBLE.
  
 15- SINCE SOME AREAS OF THE FLOOR PLAN SUBMITTED ARE
 NOT DRAWN TO A TRUE SCALE, THEN IS HARD TO VERIFY DOOR
 MANEUVERING CLEARANCES BASED ON THE PUSH SIDE, PULL
 SIDE APPROACH AND THE SPECIFIED DOOR HARDWARE. IT LOOKS
 LIKE SOME AREAS MAY NOT COMPLY. PROVIDE DIMENSIONS ON
 PLANS. CHECK THE KITCHEN AREA. CHECK IN-TAKE AND
 NURSE/MED OFFICE AND CORRIDOR ON THE RIGHT HAND SIDE.
 SEE FIGURE 404.2.4.1 FBC ACCESSIBLE AND REVISE AS
 REQUIRED.
  
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved