2018-04-24 12:19:082ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT NOT COMPLIED 10. PROVIDE DETAIL FOR
 THE SHOWER PANS. 901.2.1 THE RESPONSE LETTER FROM
 ENGINEER STATED THE ARCHITECT WOULD PROVIDE THAT THE
 RESPONSE LETTER FROM THE ARCHITECT STATED THE ENGINEER
 WOULD PROVIDE THE DETAIL.
  
 NEW COMMENT
 1. THE NEW SHOWER IN THE EXISTING BATHROOM 5+6 SHALL
 COMPLY WITH ONE OF THE ACCESSIBLE SHOWER STALL
 DIMENSIONS. THE DEPTH OF 36" BUT 48" DOES NOT COMPLY IT
 SHALL BE 60"MIN OF 36" INSIDE DIMENSION. PER FBC ACC
 608.2.1 608.2.2, 608.2.3
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  