| Plan Review Notes For Permit 18010936 |
| Permit Number |
18010936 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-24 12:19:08 | 2ND REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | PREVIOUS COMMENT NOT COMPLIED 10. PROVIDE DETAIL FOR | | | THE SHOWER PANS. 901.2.1 THE RESPONSE LETTER FROM | | | ENGINEER STATED THE ARCHITECT WOULD PROVIDE THAT THE | | | RESPONSE LETTER FROM THE ARCHITECT STATED THE ENGINEER | | | WOULD PROVIDE THE DETAIL. | | | | | | NEW COMMENT | | | 1. THE NEW SHOWER IN THE EXISTING BATHROOM 5+6 SHALL | | | COMPLY WITH ONE OF THE ACCESSIBLE SHOWER STALL | | | DIMENSIONS. THE DEPTH OF 36" BUT 48" DOES NOT COMPLY IT | | | SHALL BE 60"MIN OF 36" INSIDE DIMENSION. PER FBC ACC | | | 608.2.1 608.2.2, 608.2.3 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|