Plan Review Notes
Plan Review Notes For Permit 18010936
Permit Number 18010936
Review Stop B
Sequence Number 2
Notes
Date Text
2018-04-26 19:10:08SECOND BUILDING REVIEW CHECKLIST
 CODE: FBC 6TH EDITION (2017).
  
  
 1) COMPLIED.
  
 2) SHEET A-4/ BUILDING DATA & DESIGN:
 2A)COMPLIED.
  
 2B)SEMI-COMPLIED. SPECIFY THE OCCUPANT LOAD OF THE
 LIVING/DINING AREA. SEE TABLE 1004.1.2. CLARIFY WHAT IS
 INSTITUTIONAL AREA?. CLEARLY OUTLINE ON PLAN EACH AREA.
 REVISE TOTAL OCCUPANT LOAD AS REQUIRED. NOTE: ANY
 FRACTION SHOWN ON THE OCCUPANT LOAD CALCULATIONS NEEDS
 TO BE ROUNDED UP NOT ROUNDED DOWN.
  
 ORIGINAL COMMENT:
 OCCUPANT LOAD FACTOR IS TAKEN AT 50 SQ. OCCUPANT.
 PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2
 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
 INPATIENT TREATMENT AREAS 240 GROSS
 OUTPATIENT AREAS 100 GROSS
 SLEEPING AREAS 120 GROSS
 PLEASE UPDATE PLANS.
  
 2C) SEMI-COMPLIED. INFORMATION SUBMITTED IS NOT CLEAR.
 RESPONSE LETTER STATES I-1 ALCOHOL AND DRUG
 CENTERS/CONGREGATE CARE FACILITIES AND INFORMATION ON
 SHEET A-4 SPECIFIES "FIRE PREVENTION RESIDENTIAL
 BOARDING & CARE". CLARIFY WHAT IS "FIRE PREVENTION
 RESIDENTIAL BOARDING & CARE". AND, CLEARLY DEFINE
 SPECIFIC USE. ALSO, NEED TO CLASSIFY WHICH I-1
 CONDITION IS PROPOSED AS REQUIRED BY SEC. 308.3
 FBC-BUILDING. CONDITION 1 OR CONDITION 2.
  
 ORIGINAL COMMENT:
 THE BUILDING DATA LIST THIS OCCUPANCY AS AN I-2
 OCCUPANCY PLEASE DECLARE THE END USE?
 FBC-B 308.4 INSTITUTIONAL GROUP I-2. DETOXIFICATION
 FACILITY/ NURSING HOME
 FBC-B 308.3 INSTITUTIONAL GROUP I-1. ALCOHOL AND DRUG
 CENTERS / CONGREGATE CARE FACILITIES
 FBC-B 310.6 RESIDENTIAL GROUP R-4. RESIDENTIAL GROUP
 R-4. ALCOHOL AND DRUG CENTERS, CONGREGATE CARE
 FACILITIES. RESIDENTIAL GROUP R-4 OCCUPANCY SHALL
 INCLUDE BUILDINGS, STRUCTURES OR PORTIONS THEREOF FOR
 MORE THAN FIVE BUT NOT MORE THAN 16 PERSONS, EXCLUDING
 STAFF, WHO RESIDE ON A 24-HOUR BASIS IN A SUPERVISED
 RESIDENTIAL ENVIRONMENT AND RECEIVE CUSTODIAL CARE.
 UNTIL THE END USE IS GIVEN THE LIFE SAFETY ISSUES
 CANNOT BE DETERMINED.
 FBC-B 407 GROUP I-2 DETOXIFICATION
 FBC-B 420 I-1, R-3/ R-4.
  
 2D) SEMI-COMPLIED. CLARIFY WHY THE FURNITURE LAYOUT
 ONLY SHOW THE DESK IN THE OFFICES AND THE CHAIRS ARE
 NOT SHOWN.
 NOTE: KEEP IN MIND MANEUVERING CLEARANCES REQUIRED FOR
 PROPER DOOR OPERATION.
  
 ORIGINAL COMMENT:
 PLEASE PROVIDE A FLOOR PLANS SHOWING THE FURNITURE
 LAYOUT INCLUDING BEDS TO SEE OCCUPANT LOADS FOR THE
 SLEEPING ROOMS. TO HELP IN THE DEFINING OF THE END USE.
  
 2E) COMPLIED. PLOT PLAN PROVIDED.
  
 2F)COMPLIED. PLOT PLAN PROVIDED.
  
 2G) PASSENGER LOADING ZONE SHOWN ON THE PLOT PLAN NEEDS
 TO COMPLY WITH ALL THE REQUIREMENTS OF SEC. 503.3
 FBC-ACCESSIBILITY. SEE 503.1 THRU 503.4 AND REVISE PLOT
 PLAN AS REQUIRED. ALSO, REVISE THE PARKING INFORMATION
 SHOWN ON THE PLOT PLAN SUBMITTED. PROVIDE INFORMATION
 THAT RELATES TO PROPOSED USE. THERE ARE NOT MEDICAL
 OFFICES AND DOCTORS.
  
 ORIGINAL COMMENT:
 THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 209.3 MEDICAL CARE AND LONG-TERM
 CARE FACILITIES. AT LEAST ONE PASSENGER LOADING ZONE
 COMPLYING WITH 503 SHALL BE PROVIDED AT AN ACCESSIBLE
 ENTRANCE TO LICENSED MEDICAL CARE AND LICENSED
 LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY
 EXCEEDS TWENTY-FOUR HOURS.
  
 2H)SEMI-COMPLIED. UNITS COMPLYING WITH THE UNIT
 MOBILITY TO CLEARLY SHOW COMPLIANCE WITH THE TURNING
 SPACE SEC. 805.2 FBC-ACCESSIBILITY. REVISE THE TURNING
 SPACE TO COMPLY WITH FIGURE 304.3.2 FBC-ACCESSIBILITY.
  
 ORIGINAL COMMENT:
 THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 223.2 HOSPITALS, REHABILITATION
 FACILITIES, PSYCHIATRIC FACILITIES AND DETOXIFICATION
 FACILITIES. HOSPITALS, REHABILITATION FACILITIES,
 PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES
 SHALL COMPLY WITH 223.2.
 ACCESS. CODE223.2.1 FACILITIES NOT SPECIALIZING IN
 TREATING CONDITIONS THAT AFFECT MOBILITY. IN FACILITIES
 NOT SPECIALIZING IN TREATING CONDITIONS THAT AFFECT
 MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER THAN ONE,
 OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE MOBILITY
 FEATURES COMPLYING WITH 805. ACCESSIBLE PATIENT
 BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY.
  
 2I)805 MEDICAL CARE AND LONG-TERM CARE FACILITIES.
 805.1. COMPLIED.
  
 805.2 SEMI-COMPLIED. REVISE T-SHAPED TURNING SPACE. SEE
 FIGURE 304.3.2 FBC-ACCESSIBILITY.
  
 ORIGINAL COMMENT:
 TURNING SPACE. TURNING SPACE COMPLYING WITH 304 SHALL
 BE PROVIDED WITHIN THE ROOM.
  
 805.3 . COMPLIED.
  
 805.4. UNISEX RESTROOM AND ADJACENT BATHROOM DON'T
 COMPLY WITH THE OVERLAP REQUIREMENTS OF SEC. 604.3.2
 FBC-ACCESSIBILITY.
 AND WITH RESTROOM FIXTURE CLEARANCE DETAIL SHOWN ON
 SHEET A-5. REVISE AS REQUIRED.
 (NOTE: SHOWER IS NOT DRAWN TO SCALE IN THIS ROOM. ALSO,
 SOME ROOMS AND CORRIDORS ARE NOT DRAWN TO THE SPECIFIED
 DIMENSIONS. PLEASE VERIFY THAT ALL SPECIFIED DIMENSIONS
 WILL BE PROVIDED IN FIELD TO AVOID CONFLICTS/DELAYS).
  
 ORIGINAL COMMENT:
 TOILET AND BATHING ROOMS. TOILET AND BATHING ROOMS THAT
 ARE PROVIDED AS PART OF A PATIENT OR RESIDENT SLEEPING
 ROOM SHALL COMPLY WITH 603. WHERE PROVIDED, NO FEWER
 THAN ONE WATER CLOSET, ONE LAVATORY, AND ONE BATHTUB OR
 SHOWER SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF
 603 THROUGH 610.
  
 2J)COMPLIED.
  
 2K) THE CLEAR FLOOR SPACE DRAWN ON SHEET A-7 IS NOT TO
 SCALE. IT DOESN'T MEASURE 30"X48". REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE ) 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2K(1) COMPLIED.
  
 2K(2) COMPLIED.
  
 2K)(3) COMPLIED.
  
 2K)(4) COMPLIED.
  
 3) SHEET A-4 CERTIFICATION FOR DESIGN COMPLIANCE:
 3A) COMPLIED.
  
 3B) COMPLIED.
  
 3C) COMPLIED.
  
 3D) THE DESIGN PRESSURES SHOWN ARE TOO LOW BASED ON THE
 MEAN ROOF HEIGHT SPECIFIED (30'). REVISE AS REQUIRED.
 AND, CLEARLY INDICATE THAT DESIGN PRESSURES ARE NOMINAL
 DESIGN PRESSURES (VASD).
  
 ORIGINAL COMMENT:
 PLEASE UPDATE WALL PRESSURES PROVIDE A CHART IN VASD
 FOR 10 SQ. FT., 20 SQ. FT. 50 SQ. FT. & 100 SQ. FT. FOR
 WALL ZONES 4 & 5.
  
 3E) THE DESIGN PRESSURES SHOWN ARE TOO LOW BASED ON THE
 MEAN ROOF HEIGHT SPECIFIED (30'). REVISE AS REQUIRED.
 AND, CLEARLY INDICATE THAT DESIGN PRESSURES ARE NOMINAL
 DESIGN PRESSURES (VASD).
  
 ORIGINAL COMMENT:
 THE DESIGN PRESSURE CHART FOR THE ROOF ZONES 1,2 & 3 IS
 MARKED NOT APPLICABLE, THE PLANS INDICATE A MEAN ROOF
 HEIGHT OF 20 FT. AND 4 FOOT PARAPET. ROOF ZONES 1, 2 &
 3 NOT APPLICABLE. PLEASE NOTE THE PARAPET ON THE NORTH
 SIDE OF THE BUILDING IS BETWEEN 18 -24 INCHES TALL THUS
 CREATING ROOF ZONE 3.
 2017 FBC-B TABLE 1609.6.2, ASCE 7-10.
  
 3F) COORDINATE WITH ITEMS # 3D AND #3E ABOVE.
  
 ORIGINAL COMMENT:
 PLEASE PROVIDE THE PRESSURES FOR ALL ROOF ZONES IN
 VASD. THE MECHANICAL SHEET M3.3 SHOWS NEW ROOF TOP
 CURBS AND DOWN UNITS AS WELL AS A/C STANDS IT APPEARS
 THERE WILL BE ROOFING WORK INVOLVED AS WELL AS NEW ROOF
 TOP OPENINGS. MECHANICAL SHEET M3.3 DETAILS I &J
 INDICATE SEE ARCHITECTURAL SHEETS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 5) NEED ALL THE PRODUCT APPROVALS (2 COPIES). NOTE:
 PRODUCT APPROVAL MAY BE SUBMITTED LATER AS "DEFERRED
 SUBMITTAL" AFTER THE PERMIT IS ISSUED, BUT BEFORE ANY
 INSPECTIONS TO AVOID CONFLICT DELAYS.
  
 ORIGINAL COMMENT:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 6) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 9)COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
  
 10) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED./ 2017
 FBC-B 1604.4 ANALYSIS.
 FOR ROOF TOP A/C STAND PRODUCT APPROVAL PROVIDE A (2)
 COPIES OF THE PRODUCT APPROVAL REVIEWED BY THE DESIGNER
 OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 11) COORDINATE WITH ITEM #5 ABOVE.
  
 ORIGINAL COMMENT:
 2017 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND APPLIANCES
 REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16 FEET , SUCH ACCESS
 SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS OF
 ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR
 FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL
 SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH OR
 WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 13) PLEASE NOTE A THOROUGH REVIEW COULD NOT BE
 COMPLETED IN THIS REVIEW AND DEPENDING ON THE RESPONSE
 COMMENTS ADDITIONAL COMMENTS MAY OCCUR ON THE FOLLOWING
 REVIEWS. 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved