Plan Review Notes
Plan Review Notes For Permit 18010936
Permit Number 18010936
Review Stop P
Sequence Number 1
Notes
Date Text
2018-02-15 14:32:311ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE OCCUPANT LOAD PLUMBING FIXTURE COUNT
 BREAKDOWN FOR EMPLOYEES, VISITORS AND PATIENTS. PER FBC
 TABLE 403.1
  
 2. WHAT TYPE OF FACILITY IS THIS GOING TO BE. PER WPB
 AMEND TO FBC 107.2.1
  
 3. SHOW COMPLIANCE WITH FBC ACC 610.3 SHOWER
 COMPARTMENT SEATS.
 WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS,
 AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT
 IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN
 TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE
 BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
  
 4. GRAB BARS SHALL BE FROM FINISH FLOOR MEASURED TO THE
 TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 5. PROVIDE THE DIMENSIONS FOR SHOWER ON EXTERIOR WALL
 IN BATHROOM 5+6. 901.2.1
  
 6. SHOW COMPLIANCE WITH FBC ACC
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL.
  
 7. SHOW COMPLIANCE WITH FBC ACC 608.3.1 TRANSFER TYPE
 SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES (455 MM) FROM THE CONTROL WALL.
  
 8. THE SHOWER IN BATHROOM 7+8 SHALL BE VENTED BEFORE IT
 CONNECTS TO THE BUILDING DRAIN. PER FBC PL 901.2.1
  
 9. THE DETAILS FOR THE GREASE INTERCEPTOR SHALL COMPLY
 WITH WPB UTILITIES DEPT STANDARD DETAIL GS-7
  
 10. PROVIDE DETAIL FOR THE SHOWER PANS. 901.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  