| Date |
Text |
| 2018-02-08 11:38:36 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18010936 |
| | 2/8/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-2.2: THE MECHANICAL VENTILATION FOR THE |
| | FACILITY SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE |
| | WITH THE FBC-17 MECHANICAL, AND ASHRAE 170-2008- SEE |
| | SECTION 407.1. PLEASE PROVIDE CALCULATIONS AND DESIGN |
| | PARAMETERS FOR THE VENTILATION SYSTEM IN ACCORDANCE |
| | WITH TABLE 7-1 ASHRAE 170. PLEASE NOTE THAT THE O/A |
| | CALCULATION FOR AHU-4 ON THE PLANS IS NOT IN COMPLIANCE |
| | WITH TABLE 403.1.1 FBC-17 MECHANICAL WHICH REQUIRES |
| | DINING ROOMS TO BE CALCULATED AT 70 PERSONS PER 1000 |
| | SQ. FT. AT 7.5 CFMS PER PERSON + 0.18 CFMS PER SQ. FT. |
| | |
| | 2) M-2.2: PLEASE SHOW COMPLIANCE WITH SECTION 6.3.1 |
| | ASHRAE 170-2008 WHICH REQUIRES THE O/A INTAKES TO BE |
| | LOCATED A MINIMUM OF 25 FT. FROM EXHAUST AND VENT |
| | DISCHARGES. |
| | |
| | 3) M-2.2: PERTAINING TO THE O/A INTAKES, INDICATE HOW |
| | COMPLIANCE WITH SECTION 401.5 AND TABLE 401.5 WILL BE |
| | MET. |
| | |
| | 4) INDICATE THE AIR FILTRATION SYSTEM AND SUPPLY AIR |
| | OUTLETS ARE IN COMPLIANCE WITH TABLES 6-1 & 6-2 ASHRAE |
| | 170. |
| | |
| | 5) M3-3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE CONDENSER STAND AND MOUNTING OF THE |
| | CONDENSERS TO THE STAND. PROVIDE ENGINEERING FOR THE |
| | STAND OR SUBMIT A VALID FL. PRODUCT APPROVAL OR |
| | MIAMI-DADE NOA FOR THE STAND APPROVED BY THE EOR. SHOW |
| | ON THE PLAN HOW THE STAND IS ATTACHED TO THE STRUCTURE- |
| | SECTION 301.15. |
| | |
| | 6) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR |
| | HANDLERS THAT INDICATES THE TYPES AND SIZES OF PIPINGS, |
| | PIPING RUNS, AND TERMINATION LOCATIONS- SECTION 307. |
| | |
| | 7) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE |
| | KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION SYSTEM. |
| | PLEASE NOTE THAT COMPLIANCE WITH SECTION 508.1.1 MAKEUP |
| | AIR TEMPERATURE AND SECTION 301.15 WIND RESISTANCE WILL |
| | BE REQUIRED. |
| | |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GAS-FIRED WATER HEATER AND COOKING APPLIANCES, AND |
| | INDICATE HOW COMBUSTION AIR IS BEING PROVIDED. PROVIDE |
| | THE MEANS AND THE CALCULATIONS IN ACCORDANCE WITH |
| | SECTION FBC-17 FUEL GAS. |
| | |
| | 9) PROVIDE A VENTING PLAN FOR THE GAS WATER HEATER- |
| | SECTION 503 FBC-17 FUEL GAS. SHOW THE TYPE AND SIZE OF |
| | VENT FLUE, FLUE RUN AND TERMINATION LOCATION. ALL SHALL |
| | BE IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND |
| | PRODUCT LISTINGS. |
| | |
| | 10) PLEASE REFER TO SECTION C403.2.8 FBC-17 ENERGY |
| | CONSERVATION AND SHOW COMPLIANCE: |
| | |
| | C403.2.8 KITCHEN EXHAUST SYSTEMS. REPLACEMENT AIR |
| | INTRODUCED DIRECTLY INTO THE EXHAUST HOOD CAVITY SHALL |
| | NOT BE GREATER THAN 10 PERCENT OF THE HOOD EXHAUST |
| | AIRFLOW RATE. CONDITIONED SUPPLY AIR DELIVERED TO ANY |
| | SPACE SHALL NOT EXCEED THE GREATER OF THE FOLLOWING: |
| | |
| | 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE |
| | HEATING OR COOLING LOAD. |
| | |
| | 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER |
| | AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS |
| | CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT |
| | REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS |
| | RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION |
| | OF ADJACENT SPACES. |
| | |
| | WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS |
| | GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A |
| | FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE |
| | WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST |
| | RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY |
| | WITH ONE OF THE FOLLOWING: |
| | |
| | 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL |
| | BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED. |
| | |
| | 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75 |
| | PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS |
| | THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT |
| | AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY |
| | TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION |
| | AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE, |
| | EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND |
| | IDLE. |
| | |
| | 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT |
| | RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON |
| | NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW. |
| | |
| | WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER |
| | APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM |
| | ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL |
| | BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE |
| | DUTY RATING UNDER THE HOOD OR HOOD SECTION. |
| | |
| | EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE |
| | REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE |
| | EXHAUSTED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |