Plan Review Notes
Plan Review Notes For Permit 18010936
Permit Number 18010936
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-08 11:38:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18010936
 2/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2.2: THE MECHANICAL VENTILATION FOR THE
 FACILITY SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH THE FBC-17 MECHANICAL, AND ASHRAE 170-2008- SEE
 SECTION 407.1. PLEASE PROVIDE CALCULATIONS AND DESIGN
 PARAMETERS FOR THE VENTILATION SYSTEM IN ACCORDANCE
 WITH TABLE 7-1 ASHRAE 170. PLEASE NOTE THAT THE O/A
 CALCULATION FOR AHU-4 ON THE PLANS IS NOT IN COMPLIANCE
 WITH TABLE 403.1.1 FBC-17 MECHANICAL WHICH REQUIRES
 DINING ROOMS TO BE CALCULATED AT 70 PERSONS PER 1000
 SQ. FT. AT 7.5 CFMS PER PERSON + 0.18 CFMS PER SQ. FT.
  
 2) M-2.2: PLEASE SHOW COMPLIANCE WITH SECTION 6.3.1
 ASHRAE 170-2008 WHICH REQUIRES THE O/A INTAKES TO BE
 LOCATED A MINIMUM OF 25 FT. FROM EXHAUST AND VENT
 DISCHARGES.
  
 3) M-2.2: PERTAINING TO THE O/A INTAKES, INDICATE HOW
 COMPLIANCE WITH SECTION 401.5 AND TABLE 401.5 WILL BE
 MET.
  
 4) INDICATE THE AIR FILTRATION SYSTEM AND SUPPLY AIR
 OUTLETS ARE IN COMPLIANCE WITH TABLES 6-1 & 6-2 ASHRAE
 170.
  
 5) M3-3: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE CONDENSER STAND AND MOUNTING OF THE
 CONDENSERS TO THE STAND. PROVIDE ENGINEERING FOR THE
 STAND OR SUBMIT A VALID FL. PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE STAND APPROVED BY THE EOR. SHOW
 ON THE PLAN HOW THE STAND IS ATTACHED TO THE STRUCTURE-
 SECTION 301.15.
  
 6) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLERS THAT INDICATES THE TYPES AND SIZES OF PIPINGS,
 PIPING RUNS, AND TERMINATION LOCATIONS- SECTION 307.
  
 7) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION SYSTEM.
 PLEASE NOTE THAT COMPLIANCE WITH SECTION 508.1.1 MAKEUP
 AIR TEMPERATURE AND SECTION 301.15 WIND RESISTANCE WILL
 BE REQUIRED.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRED WATER HEATER AND COOKING APPLIANCES, AND
 INDICATE HOW COMBUSTION AIR IS BEING PROVIDED. PROVIDE
 THE MEANS AND THE CALCULATIONS IN ACCORDANCE WITH
 SECTION FBC-17 FUEL GAS.
  
 9) PROVIDE A VENTING PLAN FOR THE GAS WATER HEATER-
 SECTION 503 FBC-17 FUEL GAS. SHOW THE TYPE AND SIZE OF
 VENT FLUE, FLUE RUN AND TERMINATION LOCATION. ALL SHALL
 BE IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND
 PRODUCT LISTINGS.
  
 10) PLEASE REFER TO SECTION C403.2.8 FBC-17 ENERGY
 CONSERVATION AND SHOW COMPLIANCE:
  
 C403.2.8 KITCHEN EXHAUST SYSTEMS. REPLACEMENT AIR
 INTRODUCED DIRECTLY INTO THE EXHAUST HOOD CAVITY SHALL
 NOT BE GREATER THAN 10 PERCENT OF THE HOOD EXHAUST
 AIRFLOW RATE. CONDITIONED SUPPLY AIR DELIVERED TO ANY
 SPACE SHALL NOT EXCEED THE GREATER OF THE FOLLOWING:
  
 1.THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
  
 2.THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
  
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
  
 1.NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR SHALL
 BE TRANSFER AIR THAT WOULD OTHERWISE BE EXHAUSTED.
  
 2.DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
  
 3.LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
  
 WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER
 APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM
 ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL
 BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE
 DUTY RATING UNDER THE HOOD OR HOOD SECTION.
  
 EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE
 REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved