| 2018-02-15 14:43:45 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. |
| | |
| | 2. SHOW ON THE RISER TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, AND THE EHD NUMBER OF |
| | CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE IF |
| | BEING USED. WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 3. SHOW ON THE RISER TYPE OF GAS, (LP OR NATURAL). |
| | |
| | 5. SHOW ON THE RISER THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND/OR SYSTEM PER THE FBC-2014 FUEL GAS |
| | APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4) & 2014 |
| | FUEL GAS CODE SEC. 402.4.1. |
| | |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2014 FUEL GAS CODE SEC. 304. |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. |
| | |
| | 8. PROVIDE A SINGLE DETAIL SHOWING THE TYPE, LOCATION, |
| | LENGTH, SIZE AND TERMINATION OF THE GAS VENTS PER |
| | FBC-2014 FUEL GAS CODE SEC. 502 THRU 505. |
| | |
| | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| | |
| | 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, |
| | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY |
| | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK |
| | PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS |
| | ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF |
| | THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS |
| | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED |
| | PER NFPA 58 SECTION 3-2.2.7(H). |
| | |
| | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW |
| | CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO |
| | BE DOWN STREAM OF MANUAL VALVE. |
| | |
| | 13. SHOW THE REGULATORS ON RISER |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |