| 2018-01-29 13:47:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 1 - THERE IS NO ADDRESS INDICATED WITHIN THE |
| | TITLE BLOCK OF ANY PAGE. AN ADDRESS IS REQUIRED TO |
| | ENSURE ACCURATE LOCATION IDENTIFICATION. |
| | |
| | ADDITIONALLY, PLEASE ENSURE THAT THE ADDRESS IS |
| | CORRECT, THERE IS NO MEDICAL WAY IN WEST PALM BEACH. |
| | THERE IS A MEDICAL CENTER WAY, PLEASE CLARIFY. |
| | |
| | PER NFPA 1: |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS ANDSPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE AN ACCURATE ADDRESS. |
| | |
| | |
| | |
| | 2) SHEET A 4 - THERE IS NO INDICATION OF ANY COMPLIANCE |
| | OF THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 6TH EDITION OF FLORIDA FIRE PREVENTIO |
| | N CODE INCLUDING THE 2015 EDITION OF NFPA 1 AND NFPA |
| | 101 AND ALL OTHER APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2013 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2013 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2013 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2013 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| | |
| | PLEASE PROVIDE FOR THE REVIEW AND APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 3) SHEET A 4 - THERE IS AN INDICATION STATED THIS IS A |
| | GRUOP: INSTITUTIONAL I2. WHAT WAS THE OCCUPANCY |
| | PREVIOUSLY AND WHAT IS THE OCCUPANCY ACCORDING TO THE |
| | FFPC. |
| | |
| | PER NFPA 1: |
| | 1.7.12.5 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE CHANGE OF OCCUPANCY OF ANY EXISTING BUILDING. |
| | |
| | PER NFPA 101: |
| | 6.1 CLASSIFICATION OF OCCUPANCY. |
| | 6.1.1 GENERAL. |
| | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| | BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR |
| | STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 |
| | THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE |
| | SUBJECT TO THE RULING OF THE AUTHORITY HAVING |
| | JURISDICTION WHERE THERE IS A QUESTION OF PROPER |
| | CLASSIFICATION IN ANY INDIVIDUAL CASE. |
| | |
| | ADDITIONALLY, PLEASE ENSURE THAT ALL WINDOWS MEET THE |
| | REQUIREMENTS PER THE APPLICABLE FFPC OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | PLEASE PROVIDE DETAILS OF WHAT THIS OCCUPANCY'S |
| | ACTIVITIES AND THE OCCUPANCY CLASSIFICATION PER THE |
| | FFPC. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 2 - THERE IS A REAR EXIT INDICATED LEADING |
| | TO A FENCED-IN AREA WITH A GATE. THIS AREA IS NOT A |
| | PUBLIC WAY, BUT EXIT ACCESS. THE GATE APPEARS TO BE THE |
| | EXIT. DOES THIS GATE LEAD TO A PUBLIC WAY? |
| | |
| | PER NFPA 101: |
| | |
| | 7.7 DISCHARGE FROM EXITS. |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT |
| | DISCHARGE, UNLESS OTHERWISE PROVIDED IN |
| | 7.7.1.2 THROUGH 7.7.1.4. |
| | 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS |
| | OF THE EXIT DISCHARGE SHALL BE OF THE REQUIRED WIDTH |
| | AND SIZE TO PROVIDE ALL OCCUPANTS WITH A SAFE ACCESS TO |
| | A PUBLIC WAY. |
| | |
| | PLEASE PROVIDE DETAILS OF THE GATE AND ENTER THE GATE |
| | INTO THE DOOR SCHEDULE WITH THE APPLICABLE |
| | HARDWARE/LOACKING & LATCHING. |
| | |
| | |
| | |
| | |
| | 5) SHEET A 2 - THE DOOR SCHEDULE INDICATED THE EXIT |
| | DOORS # 3 - FRONT AND REAR AS EXISITNG; HOWEVER, NO |
| | EXIT HARDWARE OF LOCKING TYPE IS INDICATED. |
| | |
| | PER NFPA 101 |
| | 7.2 MEANS OF EGRESS COMPONENTS. |
| | 7.2.1 DOOR OPENINGS. |
| | 7.2.1.1 GENERAL. |
| | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL |
| | CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND |
| | TO THE SPECIAL REQUIREMENTS OF 7.2.1. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| | OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER |
| | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE |
| | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 |
| | THROUGH 23. |
| | |
| | PLEASE PROVIDE THE APPLICABLE INFORMATION AND AS |
| | REQUIRED BY THE OCCUPANCY CLASSIFICATION TYPE OF # 3 |
| | ABOVE. |
| | |
| | |
| | |
| | 6) SHEET A 2 - DOORS # 2 INDICATED IN THE EXIT PATH OF |
| | TRAVEL AT THE CENTER CORRIDOR AT THE INTAKE AND |
| | NURSE/MED ROOMS DO NOT HAVE THE DOOR HARDWARE NOTED. |
| | |
| | THESE DOORS CAN NOT BE LOCKED IN THE PATH OF EGRESS. |
| | |
| | PLEASE PROVIDE THE HARDWARE TYPE COMPLIANT WITH THE |
| | EGRESS CODE. |
| | |
| | |
| | |
| | |
| | 7) SHEET A 4 - THERE IS AN INDICATION THA THE BUILDING |
| | IS FULLY SPRINKLER; HOWEVER, THERE ARE NO IDICATIONS OF |
| | FIRE SPRINKLER WORK. |
| | |
| | PER NFPA 101 |
| | 9.7 AUTOMATIC SPRINKLERS. |
| | 9.7.1 GENERAL. |
| | 9.7.1.1* EACH AUTOMATIC SPRINKLER SYSTEM REQUIRED BY |
| | ANOTHER SECTION OF THIS CODE SHALL BE IN ACCORDANCE |
| | WITH ONE OF THE FOLLOWING: |
| | (1) NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER |
| | SYSTEMS |
| | (2) NFPA 13D, STANDARD FOR THE INSTALLATION OF |
| | SPRINKLER SYSTEMS IN ONE- AND TWO-FAMILY DWELLINGS AND |
| | MANUFACTURED HOMES |
| | (3) NFPA 13R, STANDARD FOR THE INSTALLATION OF |
| | SPRINKLER SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES |
| | |
| | ALL WORK OF THE FIRE SPRINKLER SYSTEM SHALL BE DONE |
| | THROUGH SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY |
| | CONTRACTORS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AND |
| | COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 8) SHEETS A 4 & E 1 - THERE ARE NO INDICATIONS OF FIRE |
| | ALARM WORK. |
| | |
| | PER NFPA 101 |
| | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 9.6.1* GENERAL. |
| | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY |
| | WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS |
| | CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER |
| | SYSTEM OR NEW FIRE ALARMSYSTEM IS REQUIRED BY THE |
| | FLORIDA BUILDING CODE. |
| | |
| | 9.6.1.3 FIRE ALARM SYSTEMS REQUIRED BY THIS CODE SHALL |
| | BE INSTALLED, TESTED, AND MAINTAINED IN ACCORDANCE WITH |
| | THE APPLICABLE REQUIREMENTS OF NFPA 70, NATIONAL |
| | ELECTRICAL CODE, AND NFPA 72, NATIONAL FIRE ALARM AND |
| | SIGNALING CODE, UNLESS IT IS AN APPROVED EXISTING |
| | INSTALLATION, WHICH SHALL BE PERMITTED TO BE CONTINUED |
| | IN USE. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AND |
| | COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 9) SHEET E 3 - AN EXIT PATH OF TRAVEL IS INDICATED ON |
| | SHEET A 4 LEADING FROM THE REAR CORRIDOR BY THE |
| | NURSE/MED DOOR # 2; HOWEVER, THERE IS NO EXIT SIGN IN |
| | THE REAR CORRIDOR LEADING IN THAT DIRECTION. |
| | |
| | PLEASE ADD AN EXIT SIGN IN THE REAR CORRIDOR AT THE |
| | DOOR # 2 AT THE NURSE/MED ROOM AND SMALL CORRIDOR. |
| | |
| | |
| | |
| | 10) THERE ARE NO INDICATIONS OF FIRE EXTINGUISHERS ON |
| | ANY SHEET OF THE SUBMITTAL. |
| | |
| | PER NFPA 101 |
| | PORTABLE FIRE EXTINGUISHERS. PORTABLE FIRE |
| | EXTINGUISHERS SHALL BE PROVIDED IN ACCORDANCE WITH |
| | SECTION 9.9. |
| | |
| | 9.9* PORTABLE FIRE EXTINGUISHERS. WHERE REQUIRED BY |
| | ANOTHER SECTION OF THIS CODE, PORTABLE FIRE |
| | EXTINGUISHERS SHALL BE SELECTED, INSTALLED,INSPECTED, |
| | AND MAINTAINED IN ACCORDANCE WITH NFPA 10, STANDARD FOR |
| | PORTABLE FIRE EXTINGUISHERS. |
| | |
| | PLEASE PROVIDE LOCATIONS. |
| | |
| | |
| | 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |