Plan Review Notes
Plan Review Notes For Permit 18010936
Permit Number 18010936
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-30 09:39:142017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010936
 ADD: 4461 MEDICAL CENTER WAY
 CONT: ERETZOR CONSTRUCTION LLC
 TEL: 954-937-7041
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 30/ 2018
 ACTION: DENIED
  
 1) PLEASE CORRECT THE ADDRESS ON THE PERMIT APPLICATION
 AND THE ARCHITECTURAL SHEETS. THE PCN NUMBER
 74-43-43-06-14-000-0012 IS 4461 MEDICAL CENTER WAY.
  
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. 2017 FBC-B 101.2 ADDRESS
 IDENTIFICATION. NEW AND EXISTING BUILDINGS SHALL BE
 PROVIDED WITH APPROVED ADDRESS IDENTIFICATION.
  
 2) SHEET A-4/ BUILDING DATA & DESIGN:
 2A) THE LAST KNOWN USE WAS A BUSINESS OCC. OCULOPLASTIC
 & ORBITAL CONSULTANTS. THE PLAN LISTS THIS AS A LEVEL
 II ALTERATION. THIS IS A CHANGE IN OCCUPANCY GOVERNED
 BY THE 2017 FBC-EXISTING BUILDING CODE CHAPTER 10. SEE
 1001.2.2 CHANGE OF OCCUPANCY CLASSIFICATION OR GROUP.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION.
  
 2B) OCCUPANT LOAD FACTOR IS TAKEN AT 50 SQ. OCCUPANT.
 PLEASE REVIEW THE 2017 FBC-B TABLE 1004.1.2
 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
 INPATIENT TREATMENT AREAS 240 GROSS
 OUTPATIENT AREAS 100 GROSS
 SLEEPING AREAS 120 GROSS
 PLEASE UPDATE PLANS.
  
 2C) THE BUILDING DATA LIST THIS OCCUPANCY AS AN I-2
 OCCUPANCY PLEASE DECLARE THE END USE?
 FBC-B 308.4 INSTITUTIONAL GROUP I-2. DETOXIFICATION
 FACILITY/ NURSING HOME
 FBC-B 308.3 INSTITUTIONAL GROUP I-1. ALCOHOL AND DRUG
 CENTERS / CONGREGATE CARE FACILITIES
 FBC-B 310.6 RESIDENTIAL GROUP R-4. RESIDENTIAL GROUP
 R-4. ALCOHOL AND DRUG CENTERS, CONGREGATE CARE
 FACILITIES. RESIDENTIAL GROUP R-4 OCCUPANCY SHALL
 INCLUDE BUILDINGS, STRUCTURES OR PORTIONS THEREOF FOR
 MORE THAN FIVE BUT NOT MORE THAN 16 PERSONS, EXCLUDING
 STAFF, WHO RESIDE ON A 24-HOUR BASIS IN A SUPERVISED
 RESIDENTIAL ENVIRONMENT AND RECEIVE CUSTODIAL CARE.
 UNTIL THE END USE IS GIVEN THE LIFE SAFETY ISSUES
 CANNOT BE DETERMINED.
 FBC-B 407 GROUP I-2 DETOXIFICATION
 FBC-B 420 I-1, R-3/ R-4.
  
 2D) PLEASE PROVIDE A FLOOR PLANS SHOWING THE FURNITURE
 LAYOUT INCLUDING BEDS TO SEE OCCUPANT LOADS FOR THE
 SLEEPING ROOMS. TO HELP IN THE DEFINING OF THE END USE.
  
 2E) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 206.2.1 SITE ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 2F) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 208.1 WHERE PARKING SPACES ARE
 PROVIDED, PARKING SPACES SHALL BE PROVIDED IN
 ACCORDANCE WITH 208. SEE SECTION 502.5 REQUIREMENTS FOR
 VAN PARKING IN STRUCTURES.
  
 2G) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 209.3 MEDICAL CARE AND LONG-TERM
 CARE FACILITIES. AT LEAST ONE PASSENGER LOADING ZONE
 COMPLYING WITH 503 SHALL BE PROVIDED AT AN ACCESSIBLE
 ENTRANCE TO LICENSED MEDICAL CARE AND LICENSED
 LONG-TERM CARE FACILITIES WHERE THE PERIOD OF STAY
 EXCEEDS TWENTY-FOUR HOURS.
  
 2H) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 223.2 HOSPITALS, REHABILITATION
 FACILITIES, PSYCHIATRIC FACILITIES AND DETOXIFICATION
 FACILITIES. HOSPITALS, REHABILITATION FACILITIES,
 PSYCHIATRIC FACILITIES AND DETOXIFICATION FACILITIES
 SHALL COMPLY WITH 223.2.
 ACCESS. CODE223.2.1 FACILITIES NOT SPECIALIZING IN
 TREATING CONDITIONS THAT AFFECT MOBILITY. IN FACILITIES
 NOT SPECIALIZING IN TREATING CONDITIONS THAT AFFECT
 MOBILITY, AT LEAST 10 PERCENT, BUT NO FEWER THAN ONE,
 OF THE PATIENT SLEEPING ROOMS SHALL PROVIDE MOBILITY
 FEATURES COMPLYING WITH 805. ACCESSIBLE PATIENT
 BEDROOMS SHALL BE DISPERSED IN A MANNER THAT IS
 PROPORTIONATE BY TYPE OF MEDICAL SPECIALTY.
  
 2I) 805 MEDICAL CARE AND LONG-TERM CARE FACILITIES.
 805.1. MEDICAL CARE FACILITY AND LONG-TERM CARE
 FACILITY PATIENT OR RESIDENT SLEEPING ROOMS REQUIRED TO
 PROVIDE MOBILITY FEATURES SHALL COMPLY WITH 805.
  
 805.2 TURNING SPACE. TURNING SPACE COMPLYING WITH 304
 SHALL BE PROVIDED WITHIN THE ROOM.
  
 805.3 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 SHALL BE PROVIDED ON EACH SIDE OF
 THE BED. THE CLEAR FLOOR SPACE SHALL BE POSITIONED FOR
 PARALLEL APPROACH TO THE SIDE OF THE BED.
  
  
 805.4 TOILET AND BATHING ROOMS. TOILET AND BATHING
 ROOMS THAT ARE PROVIDED AS PART OF A PATIENT OR
 RESIDENT SLEEPING ROOM SHALL COMPLY WITH 603. WHERE
 PROVIDED, NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY,
 AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF 603 THROUGH 610.
  
 2J) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE SIGNAGE. 703.4.1 HEIGHT ABOVE FINISH
 FLOOR OR GROUND.
  
 TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED 48 INCHES
 (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES (1525 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 2K) THE PLANS FAIL TO SHOW COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE ) 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2K(1) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2K(2) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ABA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 2K)(3) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2K)(4) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
  
 3) SHEET A-4 CERTIFICATION FOR DESIGN COMPLIANCE:
 3A) PLEASE NOTE THE RISK CATEGORY CHECKED OFF IS III.
 IN THE 2017 FBC-B TABLE 1604.5 DOES INCLUDE GROUP I-2
 OCCUPANCIES WITH AN OCCUPANT LOAD OF 50 OR MORE
 RESIDENT CARE RECIPIENTS. THE OCCUPANT LOAD WILL BE
 LESS THAN 50 WHEN CALCULATING THE FLOOR AREA STATED
 ABOVE. RISK CATEGORY WILL BE CATEGORY II.
  
 3B) THE WIND DESIGN IS GIVEN AS 160 MPH, VULT. PLEASE
 REVIEW THE 2017 FBC-B FIGURE 1609.3(1) ULTIMATE DESIGN
 WIND SPEED FOR RISK CATEGORY II BUILDINGS IS 170 MPH
 VULT.
 3C) THE WIND DESIGN CRITERIA ALSO LIST THE EXPOSURE AS
 B EXPOSURE. PLEASE UPDATE PLANS WHEN LOOKING AT WIND
 YOU LOOK FROM ALL QUADRANTS AND THERE C ROUGHNESS.
 1609.4.3 2014 FBC-B THIS SURFACE ROUGHNESS SHALL ALSO
 APPLY TO ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS
 B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET IN THE UPWIND DIRECTION AND A WIDTH GREATER
 THAN 150 FEET.
 1609.4.3 2017 FBC-B SURFACE ROUGHNESS C. OPEN TERRAIN
 WITH SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY
 LESS THAN 30 FEET . THIS CATEGORY INCLUDES FLAT OPEN
 COUNTRY, AND GRASSLANDS.
  
 3D) PLEASE UPDATE WALL PRESSURES PROVIDE A CHART IN
 VASD FOR 10 SQ. FT., 20 SQ. FT. 50 SQ. FT. & 100 SQ.
 FT. FOR WALL ZONES 4 & 5.
  
 3E) THE DESIGN PRESSURE CHART FOR THE ROOF ZONES 1,2 &
 3 IS MARKED NOT APPLICABLE, THE PLANS INDICATE A MEAN
 ROOF HEIGHT OF 20 FT. AND 4 FOOT PARAPET. ROOF ZONES 1,
 2 & 3 NOT APPLICABLE. PLEASE NOTE THE PARAPET ON THE
 NORTH SIDE OF THE BUILDING IS BETWEEN 18 -24 INCHES
 TALL THUS CREATING ROOF ZONE 3.
 2017 FBC-B TABLE 1609.6.2, ASCE 7-10.
  
 3F) PLEASE PROVIDE THE PRESSURES FOR ALL ROOF ZONES IN
 VASD. THE MECHANICAL SHEET M3.3 SHOWS NEW ROOF TOP
 CURBS AND DOWN UNITS AS WELL AS A/C STANDS IT APPEARS
 THERE WILL BE ROOFING WORK INVOLVED AS WELL AS NEW ROOF
 TOP OPENINGS. MECHANICAL SHEET M3.3 DETAILS I &J
 INDICATE SEE ARCHITECTURAL SHEETS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS AND EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 6) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 8) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 9) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
  
 10) 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED./ 2017
 FBC-B 1604.4 ANALYSIS.
 FOR ROOF TOP A/C STAND PRODUCT APPROVAL PROVIDE A (2)
 COPIES OF THE PRODUCT APPROVAL REVIEWED BY THE DESIGNER
 OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT.
  
 11) 2017 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET ,
 SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED
 MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM
 GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES?
 LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH
 OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 13) PLEASE NOTE A THOROUGH REVIEW COULD NOT BE
 COMPLETED IN THIS REVIEW AND DEPENDING ON THE RESPONSE
 COMMENTS ADDITIONAL COMMENTS MAY OCCUR ON THE FOLLOWING
 REVIEWS. 107. 2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved