2018-02-02 07:14:39PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) (REPEAT COMMENT) SPECIFY WHICH ONE OF THE APPROVED
 SYSTEMS LISTED IN THE PRODUCT APPROVAL FOR THE
 CERTAINTEED COVENTIONAL BUILT UP ROOF SYSTEM WILL BE
 USED. SUBMIT TWO SETS OF RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7
 ON PAGE 16 NOA NO. 13-0204.14.
 THE SYSTEM THAT YOU SELECTED ON PAGE 13 OF THE PRODUCT
 APPROVAL HAS A MAXIMUM DESIGN PRESSURE OF -45PSF AND
 CAN NOT BE ENHANCED TO MEET THE INCREASED PRESSURES AT
 THE PERIMETER AND CORNER AREAS OF THE ROOF PER
 LIMITATION #9. SELECT A SYSTEM WHICH ALLOWS ENHANCED
 FASTENING (LIMITATION #7) AND SUBMIT SIGNED AND SEALED
 RAS 117 CALCULATIONS IN ACCORDANCE WITH GENERAL
 LIMITATION #7 ON THE LAST PAGE OF THE PRODUCT APPROVAL.