| Plan Review Notes For Permit 18010931 |
| Permit Number |
18010931 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-02-02 07:14:39 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) (REPEAT COMMENT) SPECIFY WHICH ONE OF THE APPROVED | | | SYSTEMS LISTED IN THE PRODUCT APPROVAL FOR THE | | | CERTAINTEED COVENTIONAL BUILT UP ROOF SYSTEM WILL BE | | | USED. SUBMIT TWO SETS OF RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER 7 | | | ON PAGE 16 NOA NO. 13-0204.14. | | | THE SYSTEM THAT YOU SELECTED ON PAGE 13 OF THE PRODUCT | | | APPROVAL HAS A MAXIMUM DESIGN PRESSURE OF -45PSF AND | | | CAN NOT BE ENHANCED TO MEET THE INCREASED PRESSURES AT | | | THE PERIMETER AND CORNER AREAS OF THE ROOF PER | | | LIMITATION #9. SELECT A SYSTEM WHICH ALLOWS ENHANCED | | | FASTENING (LIMITATION #7) AND SUBMIT SIGNED AND SEALED | | | RAS 117 CALCULATIONS IN ACCORDANCE WITH GENERAL | | | LIMITATION #7 ON THE LAST PAGE OF THE PRODUCT APPROVAL. |
|