| Plan Review Notes For Permit 18010931 |
| Permit Number |
18010931 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-26 18:56:21 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY WHICH ONE OF THE APPROVED SYSTEMS LISTED IN | | | THE PRODUCT APPROVAL FOR THE CERTAINTEED COVENTIONAL | | | BUILT UP ROOF SYSTEM WILL BE USED. SUBMIT TWO SETS OF | | | RAS 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED | | | BY LIMITATION NUMBER 7 ON PAGE 16 NOA NO. 13-0204.14. | | | | | | 2) YOU INDICATED THAT THE SLOPED ROOF HAS A 3:12 SLOPE. | | | FBC-R905.2.2 REQUIRES DOUBLE UNDERLAYMENT INSTALLED IN | | | ACCORDANCE WITH FBC-R905.1.1 FOR ASPHALT SHINGLE ROOFS | | | WITH SLOPES LESS THAN 4:12. |
|