| 2018-02-08 15:36:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDED RISER DIAGRAM THAT WAS ATTACHED TO THE PLAN |
| | WAS NOT SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR |
| | THE DESIGN. PROVIDE CORRECTION. FBC 107.2.1; FS |
| | 471.003, 471.25 |
| | 2. PROVIDE CORRECT CODE REFERENCES PER CURRENT ADOPTED |
| | CODES. SEE ABOVE FOR CURRENT CODES. FBC 107.2.1 |
| | 3. PROVIDE WEATHER PROOF GFCI RECEPTACLE AT SERVICE. |
| | NEC 210.64 |
| | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 6. PROVIDE AIC RATING OF SERVICE EQUIPMENT AND PANELS. |
| | NEC 110.3, 110.9 |
| | 7. RISER DIAGRAM SHOWS A 60 AMP CIRCUIT ON # 6 WIRE |
| | FEEDING THE TRAILER. SHEET A1 STATES THAT THE FEED TO |
| | THE PANEL IS REQUIRED TO BE AT LEAST 100 AMPS. SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. PROVIDE |
| | CORRECTIONS. NEC 215.5, 230, 250.50, 250.94, 408.30; |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |