Plan Review Notes
Plan Review Notes For Permit 18010834
Permit Number 18010834
Review Stop B
Sequence Number 2
Notes
Date Text
2018-05-10 18:34:4005/14/18 TALKED TO CORY CROSS (ARCH.) TO GO OVER ROOF
 LOADS. WAITING FOR REVISED PLAN TO FINISH PROCESSING
 PERMIT.
  
  
 1-ELEVATION CERTIFICATE SUBMITTED: A) NEED ORIGINAL
 SEAL & SIGNATURE (NOT DIGITAL) AS REQ'D BY CHAPTER 472
 F.S. B) REVISE/CLARIFY THE LOWEST ADJACENT GRADE ( LAG
 13.9') AND THE HIGHEST ADJACENT GRADE (HAG 13.7").
 2- REVISE/CLARIFY ROOF LOADS. TALKED TO CORY CROSS
 (ARCH.)
 3- SUBMIT TRUSS DRAWINGS FOR REVIEW. NOTE:
 REVIEWED/APPROVED BY THE ARCHITECT.
 4- SURVEY SUBMITTED: REVISE FLOOD INFORMATION USING THE
 NEW FLOOD MAPS. AS OF OCTOBER 5TH, 2017 . NOTE: NEED TO
 COORDINATE WITH THE REQUIRED ELEVATION CERTIFICATES
 DURING CONSTRUCTION TO AVOID CONFLICTS/DELAYS.
 ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION.