| 2018-07-27 08:00:35 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18010825 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC EXISTING R504]UPDATE TO A ALTERATION-LEVEL 2. |
| | IT IS A LEVEL 2 DUE TO THE RE-CONFIGURING OF SPACES. IF |
| | THIS AFFECTS OVER 50% OF THE SPACE THAN PUT IT AS LEVEL |
| | 3. |
| | |
| | 2. CHANGE ADDRESS ON TITLE BLOCK TO THE CITY OF WEST |
| | PALM BEACH AND ADD UNIT #1. |
| | |
| | 3. [FBC EXISTING 302.4]EXISTING FLOOR PLAN AND DEMO |
| | PLAN SHOW ARCHWAY OPENINGS. PLEASE SHOW EXISTING FLOOR |
| | PLAN AS IT WAS PRIOR TO WORK BEING PERFORMED. IF THESE |
| | ROOMS ARE TO HAVE TOILETS OPEN TO THE ROOM THEN SEE THE |
| | NEXT COMMENT #4. WHILE THIS ISN'T A NEW HOME, THE NEW |
| | WORK MUST COMPLY WITH EXISTING CODE. |
| | |
| | 4.[FBC R320.1] ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, |
| | TRIPLEXES, CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT |
| | LEAST ONE BATHROOM, LOCATED WITH MAXIMUM POSSIBLE |
| | PRIVACY, WHERE BATHROOMS ARE PROVIDED ON HABITABLE |
| | GRADE LEVELS, WITH A DOOR THAT HAS A 29-INCH (737 MM) |
| | CLEAR OPENING. HOWEVER, IF ONLY A TOILET ROOM IS |
| | PROVIDED AT GRADE LEVEL, SUCH TOILET ROOMS SHALL HAVE A |
| | CLEAR OPENING OF NOT LESS THAN 29 INCHES (737 MM). |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |