| 2018-02-08 15:44:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ELECTRICAL PLAN (2 COPIES) FOR REVIEW, |
| | SIGNED AND SEALED BY A LICENSED DESIGN PROFESSIONAL OR |
| | THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| | 471.025; FBC 107.2.1, 107.3.5 |
| | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE |
| | E3706.2, E3902 |
| | 3. PROVIDE FULL FLOOR PLAN SHOWING THE SMOKE/CO ALARMS |
| | IN EACH LOCATION REQUIRED PER CODE. SHOW ON PLAN ALL |
| | EXISTING ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, |
| | SHOW AS NEW INSTALLATIONS. FBC R314.3, FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |