| Plan Review Notes For Permit 18010824 |
| Permit Number |
18010824 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-02-14 08:51:12 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PG. E3.1 DOES NOT SHOW A MEANS TO GROUP MAINS AT THE | | | SAME LOCATION PER 230.72 | | | ALL MAINS TIO BE GROUPED IN A SINGLE LOCATION. | | | | | | | | | NOIINTERSYSTEM BONDING STRIP SHOWN AT SERVICE 250.94 |
|