Plan Review Notes
Plan Review Notes For Permit 18010815
Permit Number 18010815
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-06 17:44:181ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18010815
 2/6/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C1: PLEASE UPDATE ALL APPLICABLE CODES TO THE
 FBC SIXTH EDITION 2017, AND SUBMIT AN UPDATED ENERGY
 COMPLIANCE FORM IN ACCORDANCE WITH SECTIONS C101.5 AND
 C101.5.1 FBC-17 ENERGY CONSERVATION.
  
 2) SUBMIT AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTION C403.2.1.
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.3.
  
 4) PROVIDE A DUCT LAYOUT DRAWING. CLARIFY HOW SUPPLY
 AIR WILL BE EVENLY DISTRIBUTED THROUGHOUT THE OFFICE
 SPACE AND RETUNED TO THE AIR HANDLER.
  
 5) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE BARD UNITS ON THE EXTERIOR WALL- SECTION 301.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  