2018-02-06 17:31:521ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18010806
 2/6/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C1: THE PLANS HAVE BEEN DESIGNED IN ACCORDANCE
 WITH THE FBC SIXTH EDITION 2017. PLEASE SUBMIT AN
 UPDATED ENERGY COMPLIANCE FORM- SEE SECTIONS C101.5 AND
 C101.5.1 FBC-17 ENERGY CONSERVATION.
  
 2) SUBMIT AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTION C403.2.1.
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.3.
  
 4) PROVIDE A DUCT LAYOUT DRAWING. CLARIFY HOW SUPPLY
 AIR WILL BE EVENLY DISTRIBUTED THROUGHOUT THE OFFICE
 SPACE AND RETUNED TO THE AIR HANDLER.
  
 5) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE BARD UNITS ON THE EXTERIOR WALL- SECTION 301.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  