Plan Review Notes
Plan Review Notes For Permit 18010802
Permit Number 18010802
Review Stop M
Sequence Number 2
Notes
Date Text
2018-03-08 08:42:422ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18010802
 3/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) THE 2014 ENERGYGAUGE COMPLIANCE SUBMITTAL IS
 OUTDATED. THE PLANS WERE SUBMITTED UNDER THE 2017
 FLORIDA BUILDING CODES. PLEASE PROVIDE AN UP-TO-DATE
 ENERGY REPORT- SECTION C101.5.1 FBC-17 ENERGY.
  
 2) AS PREVIOUSLY NOTED DUCT SMOKE DETECTORS ARE
 REQUIRED IN THE SUPPLY DUCTS OF THE 5-TON AIR HANDLERS.
 AN EXEMPTIOPN CAN BE APPLIED IF AIR HANDLER DATA SHEETS
 PROVIDED BY THE MANUFACTURER INDICATE THAT THE UNITS DO
 NOT HAVE THE CAPACITY TO PROVIDE OVER 2000 CFMS OF
 SUPPLY AIR AT ALL STATIC PRESSURES. PLEASE SUBMIT THE
 DATA SHEETS FROM THE MANUFACTURER OR PROVIDE THE DUCT
  
 SMOKE DETECTORS.
  
 3) THE AC CLOSET DOORS SHALL BE NON-COMBUSTIBLE IN
 ACCORDANCE WITH SECTION 602.2.1 FBC-17 MECHANICAL, AND
 SECTION C403.2.9.2 FBC-17 ENERGY CONSERVATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  