Plan Review Notes
Plan Review Notes For Permit 18010802
Permit Number 18010802
Review Stop P
Sequence Number 1
Notes
Date Text
2018-02-06 10:19:411ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A3.01 THE ACCESSIBLE SHOWER-APPEARS TO BE AN
 TRANSFER TYPE , IT SHALL HAVE A INSIDE CLEAR DIMENSIONS
 OF 36" X 36" THE DIMENSION ACROSS THE BACK WALL IS
 SHOWN AT 38 1/4" IT SHALL BE 36". PER FBC ACC 608.2.1
  
 2. THE FBC PL 403.3 REQUIRES THAT SEPARATE FACILITIES
 BE PROVIDED FOR EACH SEX THAT MAKE BOTH BATHROOMS
 REQUIRED AND EACH SHALL COMPLY TO THE FBC ACC 213.2,
 603, 604, 606
  
 3. SHT. A5.01 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 REQUIREMENTS: FBC ACC
  
 A) WATER FOUNTAINS 602.2 CLEAR FLOOR SPACE.UNITS SHALL
 HAVE A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH AND CENTERED ON THE
 UNIT. KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL
 BE PROVIDED.
 602.4 SPOUT HEIGHT.SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.SPOUT
 OUTLETS OF DRINKING FOUNTAINS FOR STANDING PERSONS
 SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 INCHES (1090
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 B) 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 C) 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
  
 D) 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305
 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 (1370 MM) MINIMUM FROM THE REAR WALL.
  
 E) 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM)
 MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON
 THE OTHER SIDE.
  
 F) 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF
 THE SEAT.
  
 G) 604.7 DISPENSERS.TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES (180 MM)
 MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 H) BREAK ROOM SINK. 606.2 CLEAR FLOOR SPACE.A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 I) SHOW DIMENSIONS ON CLEAR FLOOR SPACE. 604.3.1
 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL
 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 J) 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.IN
 TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 K) 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS.IN
 TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE PROVIDED
 ACROSS THE CONTROL WALL AND BACK WALL TO A POINT 18
 INCHES (455 MM) FROM THE CONTROL WALL.
  
 L) 610.3 SHOWER COMPARTMENT SEATS. IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY.
 THE TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM
 AND 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM
 FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR
 610.3.2.
  
 4. SHT.P1.1 UNDER PLUMBING NOTE THE CURRENT CODE THAT
 APPLIES TO THIS JOB SHALL BE THE FLORIDA BUILDING CODES
 2017 6TH EDITION WHICH WENT INTO EFFECT DEC. 31 2017.
 PLEASE CORRECT ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 5. A WATER FOUNTAIN COMPILING WITH FBC PL [BE] 410.3 IS
 REQUIRED IN THIS OCCUPANCY PER FBC PL TABLE 403.1,
 SECTION 410.3 SHALL NOT APPLY TO THIS OCCUPANCY.
  
 6. SHT. P1.1 THE FIXTURE SCHEDULE IS CALLING OUT A SIDE
 CONNECT WATER HEATER-DETAIL #4 SHOWS A TOP FEED PLEASE
 PROVIDE A DETAIL THAT SHOWS A SIDE CONNECT WATER HEATER
 WITH THE REQUIRED VACUUM BREAKER ON THE SUPPLY SIDE.
 PER FBC PL 504.2
  
 7. SHT. P1.2 THE SHOWER IS MISSING FROM THE SANITARY
 ISOMETRIC DRAWING PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 8. A LINT TRAP OR SOLIDS INTERCEPTOR IS REQUIRED ON
 DISCHARGE OF THE WASHING MACHINE. PER FBC PL 1003.6
  
 9. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved