| Plan Review Notes For Permit 18010802 |
| Permit Number |
18010802 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-29 17:02:53 | 1ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION | | | CODES | | | PERMIT #18010802 | | | 1/29/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | | AC SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY SIDE | | | OF THE 5-TON AIR HANDLER PER SECTION 606.2.1. PLEASE | | | NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE | | | MANUFACTURER'S SPECIFICATIONS INDICATES THE SYSTEM IS | | | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. | | | | | | 3) THE CORRIDOR SHALL NOT BE USED AS A RETURN AIR DUCT- | | | SECTION 601.2. RELOCATE THE RETURN GRILL AND DUCT IN | | | THE CORRIDOR BY BATH 116, OR EXTEND THE DUCT TO THE | | | AHU-1 CLOSET. | | | | | | 4) THE OUTDOOR AIR INTAKE DUCTS SHALL BE PROVIDED WITH | | | EITHER MOTORIZED OR GRAVITY SHUTOFF DAMPERS- SECTION | | | C404.2.4.3 FBC-17 ENERGY CONSERVATION | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|