2018-01-29 17:02:531ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18010802
 1/29/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 2) A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY SIDE
 OF THE 5-TON AIR HANDLER PER SECTION 606.2.1. PLEASE
 NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATES THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 3) THE CORRIDOR SHALL NOT BE USED AS A RETURN AIR DUCT-
 SECTION 601.2. RELOCATE THE RETURN GRILL AND DUCT IN
 THE CORRIDOR BY BATH 116, OR EXTEND THE DUCT TO THE
 AHU-1 CLOSET.
  
 4) THE OUTDOOR AIR INTAKE DUCTS SHALL BE PROVIDED WITH
 EITHER MOTORIZED OR GRAVITY SHUTOFF DAMPERS- SECTION
 C404.2.4.3 FBC-17 ENERGY CONSERVATION
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  