2018-01-24 08:10:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC SPECIFIED FOR DESIGN IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE ABOVE)
 2. PROVIDE SIZE OF EXISTING MAIN 1 OF 2 AND FEEDERS
 SIZES TO VERIFY SIZE IS ADEQUATE. NEC 408.30, 230.79;
 FBC 107.2.1
 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 4. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10
 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
 7. THERE IS A NOTE THAT INDICATES SOME OF THE LIGHTING
 CIRCUITS WILL BE CONTROLLED THROUGH A TIME CLOCK, BUT
 THE CIRCUITS CONTROLLED ARE NOT IDENTIFIED. PROVIDE
 CORRECTION. FBC 107.2.1; FBC EC C405.2
 8. PROVIDE WEATHER PROOF GFCI RECEPTACLE AT SERVICE.
 NEC 210.64
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  