| 2018-01-24 08:10:39 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE NEC SPECIFIED FOR DESIGN IS NOT THE CURRENT |
| | CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE ABOVE) |
| | 2. PROVIDE SIZE OF EXISTING MAIN 1 OF 2 AND FEEDERS |
| | SIZES TO VERIFY SIZE IS ADEQUATE. NEC 408.30, 230.79; |
| | FBC 107.2.1 |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | 4. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| | CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. |
| | NEC 110.10 |
| | 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 7. THERE IS A NOTE THAT INDICATES SOME OF THE LIGHTING |
| | CIRCUITS WILL BE CONTROLLED THROUGH A TIME CLOCK, BUT |
| | THE CIRCUITS CONTROLLED ARE NOT IDENTIFIED. PROVIDE |
| | CORRECTION. FBC 107.2.1; FBC EC C405.2 |
| | 8. PROVIDE WEATHER PROOF GFCI RECEPTACLE AT SERVICE. |
| | NEC 210.64 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |