Plan Review Notes
Plan Review Notes For Permit 18010802
Permit Number 18010802
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-26 13:12:222014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010802
 ADD: 2218 S. DIXIE HWY.
 CONT: PCN DEVELOPMENT INC.
 TEL: 561-302-4009
 E-MAIL: PATRICK@PCNDEVLOPMENT
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 26/ 2018
 ACTION: DENIED
  
 1) IN BOTH SETS OF ARCHITECTURAL PLANS THE SHEETS WERE
 SIGNED & DATED BUT NEVER STAMPED WITH THE ARCHITECTS
 SEAL. 61 G 1-16.003 USES OF SEAL.
  
 2) SHEET A1.01 THE COVERSHEET UNDER THE HEADING CODE
 INFORMATION LIST THE 2014 FBC AND FAMILY OF CODES. THE
 2017 FBC FAMILY OF CODES WAS ADOPTED DEC. 31/ 2017
 STATEWIDE. THE PLANS WERE SUBMITTED ON 1/22/2018
 REQUIRING THE PLANS TO BE CREATED UNDER THE 2017 FBC-B.
  
 3) SHEET A3.01 INDICATES A NEW STOREFRONT DOOR AND
 TRANSOM. SHEET A5.01 PROVIDES THE WIND DESIGN UNDER THE
 2014 FBC-B. PLEASE UPDATE THE PLANS TO THE 2017 FBC.
  
 4) SHEET A5.01 ALSO HAS THE POSITIVE AND NEGATIVE
 PRESSURES. UNDER THE WIND DESIGN CRITERIA IT HAS BOTH:
 VULT 170 MPH & VASD 132 MPH. THE PRESSURE THEMSELVES
 DOESN?T INDICATE IF THEY ARE IN VULT OR VASD.
 DEPENDING ON THE PRESSURES GIVEN SOME ARE LOW FOR VULT
 BUT HIGH FOR VASD. EXAMPLE;
 VASD/ 132 MPH. EXP. C MEAN ROOF 15 FT.
 WALL ZONE 4 @ 10 SQ. FT. -48.55. SHOULD BE -41.9 VASD.
 SHOULD BE -68.48 VULT.
 WALL ZONE 5 @ 10 SQ. FT. -67.58. SHOULD BE ?50.7 VASD.
 SHOULD BE -84.51 VULT.
 THIS IS TRUE FOR BOTH ROWS OF FIGURES.
  
 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS & TRANSOM.
  
 6) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET A3.01 IN BOTH ROOMS THE BATHROOM 114 AND THE
 LAUNDRY ROOM 117BOTH OF THE DOORS SWING OUT OVER ? OF
 THE REQUIRED EXIT SEE SECTION 2017 FBC-B 1005.7.1
 DOORS. DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE
 REQUIRED WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN
 ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY
 MORE THAN ONE-HALF.
  
 8) SHEET A3.01 DOES NOT SHOW THE LANDING ON THE
 EXTERIOR SIDE OF THE NEW DOOR AND COMPLIANCE WITH
 SECTION 404.2.4 MANEUVERING CLEARANCES OF THE 2017
 ACCESSIBILITY CODE.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 9) SHEET A3.01 HAS NOTES FOR THE ACCESSIBLE BREAK ROOM
 SINK AND MICROWAVE BUT THERE ARE NO DETAILS SHOWING
 CODE COMPLIANCE WITH: 2017 FBC-ACCESSIBILITY CODE 606.3
 HEIGHT.
  
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 THE MICROWAVE MUST COMPLY WITH THE 2017 ACCESSIBILITY
 CODE;
  
 REACH RANGES 308.2 FORWARD REACH AND OR 308.3 SIDE
 REACH AND
  
 309. OPERABLE PARTS.
 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE PROVIDED.
  
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  