| 2018-01-26 13:12:22 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18010802 |
| | ADD: 2218 S. DIXIE HWY. |
| | CONT: PCN DEVELOPMENT INC. |
| | TEL: 561-302-4009 |
| | E-MAIL: PATRICK@PCNDEVLOPMENT |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 26/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) IN BOTH SETS OF ARCHITECTURAL PLANS THE SHEETS WERE |
| | SIGNED & DATED BUT NEVER STAMPED WITH THE ARCHITECTS |
| | SEAL. 61 G 1-16.003 USES OF SEAL. |
| | |
| | 2) SHEET A1.01 THE COVERSHEET UNDER THE HEADING CODE |
| | INFORMATION LIST THE 2014 FBC AND FAMILY OF CODES. THE |
| | 2017 FBC FAMILY OF CODES WAS ADOPTED DEC. 31/ 2017 |
| | STATEWIDE. THE PLANS WERE SUBMITTED ON 1/22/2018 |
| | REQUIRING THE PLANS TO BE CREATED UNDER THE 2017 FBC-B. |
| | |
| | 3) SHEET A3.01 INDICATES A NEW STOREFRONT DOOR AND |
| | TRANSOM. SHEET A5.01 PROVIDES THE WIND DESIGN UNDER THE |
| | 2014 FBC-B. PLEASE UPDATE THE PLANS TO THE 2017 FBC. |
| | |
| | 4) SHEET A5.01 ALSO HAS THE POSITIVE AND NEGATIVE |
| | PRESSURES. UNDER THE WIND DESIGN CRITERIA IT HAS BOTH: |
| | VULT 170 MPH & VASD 132 MPH. THE PRESSURE THEMSELVES |
| | DOESN?T INDICATE IF THEY ARE IN VULT OR VASD. |
| | DEPENDING ON THE PRESSURES GIVEN SOME ARE LOW FOR VULT |
| | BUT HIGH FOR VASD. EXAMPLE; |
| | VASD/ 132 MPH. EXP. C MEAN ROOF 15 FT. |
| | WALL ZONE 4 @ 10 SQ. FT. -48.55. SHOULD BE -41.9 VASD. |
| | SHOULD BE -68.48 VULT. |
| | WALL ZONE 5 @ 10 SQ. FT. -67.58. SHOULD BE ?50.7 VASD. |
| | SHOULD BE -84.51 VULT. |
| | THIS IS TRUE FOR BOTH ROWS OF FIGURES. |
| | |
| | 5) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS & TRANSOM. |
| | |
| | 6) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) SHEET A3.01 IN BOTH ROOMS THE BATHROOM 114 AND THE |
| | LAUNDRY ROOM 117BOTH OF THE DOORS SWING OUT OVER ? OF |
| | THE REQUIRED EXIT SEE SECTION 2017 FBC-B 1005.7.1 |
| | DOORS. DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE |
| | REQUIRED WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN |
| | ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY |
| | MORE THAN ONE-HALF. |
| | |
| | 8) SHEET A3.01 DOES NOT SHOW THE LANDING ON THE |
| | EXTERIOR SIDE OF THE NEW DOOR AND COMPLIANCE WITH |
| | SECTION 404.2.4 MANEUVERING CLEARANCES OF THE 2017 |
| | ACCESSIBILITY CODE. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE OR HINGE SIDE CLEARANCE. |
| | |
| | 9) SHEET A3.01 HAS NOTES FOR THE ACCESSIBLE BREAK ROOM |
| | SINK AND MICROWAVE BUT THERE ARE NO DETAILS SHOWING |
| | CODE COMPLIANCE WITH: 2017 FBC-ACCESSIBILITY CODE 606.3 |
| | HEIGHT. |
| | |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | THE MICROWAVE MUST COMPLY WITH THE 2017 ACCESSIBILITY |
| | CODE; |
| | |
| | REACH RANGES 308.2 FORWARD REACH AND OR 308.3 SIDE |
| | REACH AND |
| | |
| | 309. OPERABLE PARTS. |
| | 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 SHALL BE PROVIDED. |
| | |
| | 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE |
| | OR MORE OF THE REACH RANGES SPECIFIED IN 308. |
| | |
| | 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH |
| | ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N) |
| | MAXIMUM. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |