| Plan Review Notes For Permit 18010787 |
| Permit Number |
18010787 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-02 03:53:42 | 1) SUBMIT ROOF DRAIN CALCULATIONS PER THE 2017 | | | FBC-PLUMBING SECS.1106.2, 1106.3. THE SIZING SHALL BE | | | BASED ON 5 INCHES OF RAIN PER HOUR. | | | 2) SHOW PROVISIONS FOR SECONDARY (EMERGENCY) ROOF | | | DRAINAGE PER 2017 FBC - -PLUMBING SEC.1108. SHT. A-5 | | | SHOWS WHAT APPEARS TO BE A RAISED ROOF CURB/EDGE AT THE | | | PERIMETER OF THE ROOF. CLARIFY. | | | 3) PAPER PLANS CANNOT BE DIGITALLY SIGNED AND SEALED | | | PER F.A.C. RULE 61G15-23.004, FL. STATUTE 471.025. | | | 4) SHT. 1 IS MISSING FROM ONE OF THE SET OF PLANS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | |
|