Plan Review Notes
Plan Review Notes For Permit 18010787
Permit Number 18010787
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-04 10:46:401ST REVIEW FBC-2017 MECHANICAL
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 515 FBC M AND REVCISE THE PLANS AND
 DETAILS TO SHOW THE REQUIRED RELIEF VENTING FOR THE
 MAUSOLEUM.
  
 MAUSOLEUM RELIEF VENT
  
 515.1 GENERAL.
 A PRESSURE RELIEF VENT SHALL BE PROVIDED FOR EACH
 CRYPT. NICHES SHALL NOT REQUIRE PRESSURE RELIEF
 SYSTEMS.
  
 515.2 MATERIALS.
 THE PRESSURE RELIEF VENT PIPE AND FITTINGS SHALL
 CONFORM TO ONE OF THE STANDARDS LISTED IN TABLES 515.2A
 AND 515.2B.
  
 TABLE 515.2A
 CRYPT PRESSURE RELIEF PIPE
 MATERIAL STANDARD
 ACRYLONITRILE BUTADIENE STYRENE (ABS) PLASTIC PIPE ASTM
 D2661, ASTM F628CSA B181.1,
 POLYLEFIN PIPE CSA CAN/CSA B181.3
 POLYVINYL CHLORIDE (PVC) PLASTIC PIPE (TYPE DWV) ASTM
 D2665, ASTM D2949, ASTM F891
  
 TABLE 515.2B
 CRYPT PRESSURE RELIEF FITTINGS
 MATERIAL STANDARD
 ACRYLONITRILE BUTADIENE STYRENE (ABS) PLASTIC PIPE ASTM
 D3311, CSA B181.1
 POLYVINYL CHLORIDE (PVC) PLASTIC PIPE (TYPE DWV) ASTM
 D3311, ASTM D2949, ASTM F891
 PLASTIC, GENERAL ASTM F409
  
 515.3 PRESSURE RELIEF VENT.
  
 FOR FAMILY MAUSOLEUM UNITS WHERE ALL CRYPTS ARE
 BORDERING AN EXTERIOR WALL, PRESSURE RELIEF VENTILATION
 SHALL BE PROVIDED FROM THE CRYPT TO THE OUTSIDE OF THE
 MAUSOLEUM THROUGH THE EXTERIOR WALL OR ROOF. FOR ALL
 OTHER MAUSOLEUM UNITS, EACH CRYPT SHALL HAVE A PRESSURE
 RELIEF VENT FROM THE CRYPT TO THE ROOF OF THE
 MAUSOLEUM. THE MINIMUM NOMINAL PIPE SIZE SHALL BE 1
 INCH (25 MM). THE SYSTEM SHALL HAVE A MINIMUM OF
 ONE-EIGHTH UNIT VERTICAL TO 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). THE PIPING SHALL NOT BE TRAPPED OR
 INSTALLED TO TRAP WATER OR CONDENSATE.
  
 515.4 TERMINATION.
  
 EXCEPT FOR FAMILY MAUSOLEUM UNITS WHERE ALL CRYPTS ARE
 BORDERING AN EXTERIOR WALL, CRYPT PRESSURE RELIEF
 SYSTEM SHALL EXTEND THROUGH THE ROOF AND TERMINATE AT
 LEAST 6 INCHES (152 MM) ABOVE THE ROOF AND AT LEAST 10
 FEET (3048 MM) FROM ANY OPENABLE OPENING, AIR INTAKE OR
 PROPERTY LINE. THE TERMINATION OF THE RELIEF SYSTEM
 PIPE SHALL BE DONE BY A ROOF AND VENT CAP COMPATIBLE
 WITH THE RELIEF PRESSURE PIPE. THE ROOF AND VENT CAP
 SHALL BE WATERPROOF. FOR FAMILY MAUSOLEUM UNITS WHERE
 ALL CRYPTS ARE BORDERING AN EXTERIOR WALL, PRESSURE
 RELIEF VENTILATION SHALL BE PROVIDED FROM THE CRYPT TO
 THE OUTSIDE OF THE MAUSOLEUM THROUGH THE EXTERIOR WALL
 OR ROOF.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER