| Plan Review Notes For Permit 18010778 |
| Permit Number |
18010778 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-02-16 18:16:56 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- STORM SHUTTERS INSTALLATION SCHEDULE IS NOT CLEAR. | | | SPECIFY SHUTTER MOUNTING CONDITIONS. MIAMI DADE IS NOT | | | A MOUNTING CONDITION. SHUTTERS GLASS SEPARATION NEEDS | | | TO BE REVISED. SEE TABLE 2 ON SHEET 5 OF 5 OF NOA | | | DRAWINGS SUBMITTED. THE SHUTTERS SPAN DIMENSION IS NOT | | | CLEAR IF THE STORM PANELS ARE MOUNTED VERTICALLY. | | | REVISE ANCHOR SPACING BASED ON THE SUBSTRATE TO RECEIVE | | | THE SHUTTERS (CONCRETE BLOCK). SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|