2018-01-26 07:10:4901/26/2018 1ST GAS REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) CITY RECORDS DO NOT SHOW A POOL HEATER AS EVER BEING
 INSTALLED AND NOT ON ANY PREVIOUS ISOMETRIC PLANS. THE
 SYSTEM IS UNDERSIZED FOR THE EXISTING GAS METER MODEL
 AL-425 MAX BTU IS 865,000. .. NOTE: IF THE EXISTING
 SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE SYSTEM
 PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3
  
 2) YOU SHOW THE EXISTING GAS METER AT 7" WC FLOWING
 425,000. PLEASE EXPLAIN FBC107.2.1.
  
 3) YOU INCLUDED SPEC MANUAL FOR A PRESSURE REGULATOR
 BUT YOUR DESIGN PRESSURE IS .5 LB PLEASE EXPLAIN. FBC
 107.2.1
  
 4) PLEASE LIST CURRENT CODE AS FBC FUEL AND GAS 2017
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER