| 2018-01-26 07:10:49 | 01/26/2018 1ST GAS REVIEW**DENIED** | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1) CITY RECORDS DO NOT SHOW A POOL HEATER AS EVER BEING | | | INSTALLED AND NOT ON ANY PREVIOUS ISOMETRIC PLANS. THE | | | SYSTEM IS UNDERSIZED FOR THE EXISTING GAS METER MODEL | | | AL-425 MAX BTU IS 865,000. .. NOTE: IF THE EXISTING | | | SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE SYSTEM | | | PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3 | | | | | | 2) YOU SHOW THE EXISTING GAS METER AT 7" WC FLOWING | | | 425,000. PLEASE EXPLAIN FBC107.2.1. | | | | | | 3) YOU INCLUDED SPEC MANUAL FOR A PRESSURE REGULATOR | | | BUT YOUR DESIGN PRESSURE IS .5 LB PLEASE EXPLAIN. FBC | | | 107.2.1 | | | | | | 4) PLEASE LIST CURRENT CODE AS FBC FUEL AND GAS 2017 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | | | | | | | |
|