| Plan Review Notes For Permit 18010661 |
| Permit Number |
18010661 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-26 06:00:27 | 1) THE GAS CODE IN EFFECT FOR THIS PERMIT IS THE 2017 | | | FBC-FUEL GAS, NOT THE 2014 AS NOTED ON THE PLANS AND | | | THE SUBMITTED SIZING TABLES. | | | 2) THE MANUFACTURER'S SPECIFICATIONS FOR THE 22 KW | | | GENERATOR SHOW THE BTU RATING OF THE THE GENERATOR AT | | | 100 % FULL LOAD 310,000 BTU'S BUT THE GAS PLAN SHOWS | | | 281,000 BTU'S. CLARIFY.SEE 2017 FBC-FUEL GAS SECS. | | | 402.1, 402.2. | | | 3) THE SIZE OF THE GAS LINE FROM THE OUTLET OF THE GAS | | | METER SHALL BE INCREASED TO 1 1/4 INCH PER 2017 | | | FBC-FUEL GAS TABLE 402.4 (2). THE MAXIMUM BTU LOAD THAT | | | CAN BE INSTALLED ON A 1/2 LB. GAS METER WITH A 1 INCH | | | LINE WITH A DISTANCE OF 45 FEET IS 284,000 BTU'S. THE | | | TOTAL BTU LOAD MUST BE TAKEN INTO ACCOUNT FOR THE | | | SIZING OF THE PIPE LINE AT THE OUTLET OF THE | | | METER.REFER TO 2017 FBC-FUEL GAS SECS.401.3, 401.4, | | | 401.8. | | | 4) THE GAS PLAN REFERENCES TABLE 402.4 (15) WHICH IS | | | FOR CSST BUT THERE IS NO CSST SHOWN ON THE GAS PLAN. | | | CLARIFY. | | | 5) IDENTIFY THE TYPE OF PIPE RUNNING THROUGH THE | | | GARAGE. IF IT IS CSST, SUBMIT THE CORRESPONDING EHD OF | | | THE SIZE CSST PIPE IN ACCORDANCE WITH TABLE 402.4 (15) | | | OF THE 2017 FBC-FUEL GAS CODE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|