2018-01-24 10:15:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE 22 KW GENERATOR SPECIFICATIONS THAT WERE
 SUBMITTED ARE FOR TWO DIFFERENT GENERAC MODELS. REMOVE
 THE SPECS. FOR THE ONE THAT WILL NOT BE INSTALLED FROM
 THE SUBMITTAL. FBC 107.2.1
  
 2) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING FOR
 THE AMERICAST GENERATOR PAD THAT LISTS THE SPECIFIC
 MODEL GENERATOR THAT YOU PLAN TO INSTALL. FBC-R301.1