2018-03-01 09:08:191ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE LAY OUT FOR THE TRANSFER SHOWER DOES NOT ALLOW
 FOR THE REQUIRED CLEAR FLOOR SPACE OF 36"X48" IT SHALL
 BE MEASURED FROM CONTROL WALL EXTENDING 48" ACROSS THE
 OPENING OF THE SHOWER, IF THE CONTROL WALL IS REVERSED
 TO THE WALL ADJACENT TO THE HALLWAY IT WILL COMPLY. PER
 FBC ACC 608.2.1
  
 2. PLEASE SHOW THE DIMENSIONS FOR GRAB BAR ON REAR WALL
 OF THE TOILET IT SHALL EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
  
 3. THE FLOOR SINK SHOWN ON THE SANITARY ISOMETRIC
 DRAWING IS NOT VENTED. IT SHALL COMPLY WITH FBC PL
 901.2.1, 910.1
  
 4. THE FLOOR SINK ON THE ISOMETRIC SHALL HAVE A TRAP
 PRIMER. PER FBC PL 1002.4.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  