| 2018-03-01 09:08:19 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE LAY OUT FOR THE TRANSFER SHOWER DOES NOT ALLOW | | | FOR THE REQUIRED CLEAR FLOOR SPACE OF 36"X48" IT SHALL | | | BE MEASURED FROM CONTROL WALL EXTENDING 48" ACROSS THE | | | OPENING OF THE SHOWER, IF THE CONTROL WALL IS REVERSED | | | TO THE WALL ADJACENT TO THE HALLWAY IT WILL COMPLY. PER | | | FBC ACC 608.2.1 | | | | | | 2. PLEASE SHOW THE DIMENSIONS FOR GRAB BAR ON REAR WALL | | | OF THE TOILET IT SHALL EXTEND FROM THE CENTERLINE OF | | | THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 | | | INCHES MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2 | | | | | | 3. THE FLOOR SINK SHOWN ON THE SANITARY ISOMETRIC | | | DRAWING IS NOT VENTED. IT SHALL COMPLY WITH FBC PL | | | 901.2.1, 910.1 | | | | | | 4. THE FLOOR SINK ON THE ISOMETRIC SHALL HAVE A TRAP | | | PRIMER. PER FBC PL 1002.4.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|