2018-01-29 11:10:471ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE LENGTH OF THE SHOWER IS SHOWN AS 50" THIS DOES
 NOT COMPLY WITH ANY OF THE THREE TYPES OF ACC SHOWERS
 PLEASE COMPLY WITH FBC ACC 608.2.1 OR 608.2.2 OR
 608.2.3
  
 2. PROVIDE DETAILS FOR MOUNTING THE GRAB BARS OFF THE
 SIDE AND BACK WALLS OF THE SHOWER. PER FBC ACC 608.3.1
 OR 608.3.2 OR 608.3.3
  
 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 610.3
  
 4. PLEASE PROVIDE DETAILS FOR FBC ACC
 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL.
 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHE SLONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
  
 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER FBC ACC 604.7
  
 6. PLEASE PROVIDE AN ISOMETRIC DRAWING FOR THE SANITARY
 AND WATER, SHOWING THE REQUIRED BACKFLOWS ON THE COFFEE
 AND ICE MACHINES, AIR HAMMER ARRESTORS, TRAP PRIMERS.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 7. FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  