| 2018-01-29 11:10:47 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE LENGTH OF THE SHOWER IS SHOWN AS 50" THIS DOES |
| | NOT COMPLY WITH ANY OF THE THREE TYPES OF ACC SHOWERS |
| | PLEASE COMPLY WITH FBC ACC 608.2.1 OR 608.2.2 OR |
| | 608.2.3 |
| | |
| | 2. PROVIDE DETAILS FOR MOUNTING THE GRAB BARS OFF THE |
| | SIDE AND BACK WALLS OF THE SHOWER. PER FBC ACC 608.3.1 |
| | OR 608.3.2 OR 608.3.3 |
| | |
| | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC 610.3 |
| | |
| | 4. PLEASE PROVIDE DETAILS FOR FBC ACC |
| | 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42 |
| | INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL. |
| | 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36 |
| | INCHE SLONG MINIMUM AND EXTEND FROM THE CENTERLINE OF |
| | THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 |
| | INCHES MINIMUM ON THE OTHER SIDE. |
| | |
| | 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. PER FBC ACC 604.7 |
| | |
| | 6. PLEASE PROVIDE AN ISOMETRIC DRAWING FOR THE SANITARY |
| | AND WATER, SHOWING THE REQUIRED BACKFLOWS ON THE COFFEE |
| | AND ICE MACHINES, AIR HAMMER ARRESTORS, TRAP PRIMERS. |
| | PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 7. FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES.TEMPERED WATER SHALL BE DELIVERED FROM |
| | LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC |
| | TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |