2018-01-24 10:31:121ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18010633
 1/2/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M2.1: SMOKE DETECTORS ARE REQUIRED IN THE COMMON
 RETURN AIR PLENUM OF THE HP SYSTEMS- SECTION 606.2.2
 EXCEPTION 2. PLEASE SHOW THE LOCATION(S) OF THE SMOKE
 DETECTORS AND PROVIDE CONTROL SEQUENCE AND SUPERVISORY
 INFORMATION- SECTIONS 606.4 & 606.4.1.
  
 2) M2.1 & M2.2: PLEASE LABEL THE EF BY THE O/A SHAFT
 AND INCKUDE IN THE FAN SCHEDULE. IT APPEARS THAT THE
 EXHAUST DUCT RUN IS INCOMPLETE.
  
 3) M2.2: REVISE THE O/A CALCULATIONS TO SHOW THE
 CORRECT NUMBER OF OCCUPANTS IN THE CONFERENCE ROOMS AND
 REQUIRED O/A PER TABLE 403.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  