| 2018-01-24 10:31:12 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18010633 | | | 1/2/3/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M2.1: SMOKE DETECTORS ARE REQUIRED IN THE COMMON | | | RETURN AIR PLENUM OF THE HP SYSTEMS- SECTION 606.2.2 | | | EXCEPTION 2. PLEASE SHOW THE LOCATION(S) OF THE SMOKE | | | DETECTORS AND PROVIDE CONTROL SEQUENCE AND SUPERVISORY | | | INFORMATION- SECTIONS 606.4 & 606.4.1. | | | | | | 2) M2.1 & M2.2: PLEASE LABEL THE EF BY THE O/A SHAFT | | | AND INCKUDE IN THE FAN SCHEDULE. IT APPEARS THAT THE | | | EXHAUST DUCT RUN IS INCOMPLETE. | | | | | | 3) M2.2: REVISE THE O/A CALCULATIONS TO SHOW THE | | | CORRECT NUMBER OF OCCUPANTS IN THE CONFERENCE ROOMS AND | | | REQUIRED O/A PER TABLE 403.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|