| Notes |
| Date |
Text |
| 2018-01-22 12:19:49 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- ENGINEER LETTER SUBMITTED FOR THE ROOF TO WALL | | | CONNECTIONS NEED TO BE REVISED. ACCORDING TO SEC. | | | R301.2.1.4 FBC-RESIDENTIAL 5TH EDITION (2014) THIS | | | BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". | | | REVISE AS REQUIRED OR PROVIDE COMPLETE ENGINEERING | | | ANALYSIS. | | | | | | 2- ROOF TILE ADHESIVE PRODUCT APPROVAL FL6332-R8 | | | SUBMITTED: CLEARLY MARK ON THE PRODUCT APPROVAL THE | | | PADDY SIZE TO BE INSTALLED TO VERIFY COMPLIANCE WITH | | | THE DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: KEEP IN MIND THAT THIS BUILDING IS LOCATED IN | | | EXPOSURE "D". COORDINATE WITH ITEM #1 ABOVE. | | | | | | 3- PROVIDE SKYLIGHT CURRENT PRODUCT APPROVAL. PRODUCT | | | APPROVAL FL2418-R9 SUBMITTED IS FOR THE 2014 CODE. THE | | | CURRENT CODE IS THE FBC-6TH EDITION (2017). PROVIDE 2 | | | COPIES OF CURRENT PRODUCT APPROVAL. FAC 61G20-3.001. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|