| Plan Review Notes For Permit 18010595 |
| Permit Number |
18010595 |
|
| Review Stop |
G |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-08-08 05:36:41 | 1) THE SIZING TABLE THAT HAS BEEN SUBMITTED FOR THE PE | | | PIPE IS NOT FROM THE 2017 FBC-FUEL GAS CODE. SUBMIT TWO | | | COPIES FROM THE 2017 FBC. WPB AMEND. TO FBC SEC. 107.1, | | | 107.2.1. | | | 2) MANUFACTURER'S SPECIFICATIONS HAVE BEEN SUBMITTED | | | FOR TWO DIFFERENT GAS GRILLS. ONE SET IS FOR A WOLF | | | GRILL AND THE OTHER IS FOR AN ARTISAN. WHICH ONE IS | | | BEING INSTALLED? SUBMIT TWO COPIES OF THE | | | MANUFACTURER'S SPECIFICATIONS FOR THE GRILL BEING | | | INSTALLED AND REMOVE THE SPECIFICATIONS THAT ARE NOT | | | APPLICABLE.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) THE PLANS SHOW AN EXISTING GRILL TO BE RELOCATED YET | | | YOU HAVE SUBMITTED SPECIFICATIONS FOR A NEW GRILL. WHAT | | | IS THE SCOPE OF WORK BEING DONE? IS THE GRILL NEW OR | | | EXISTING? AT THIS POINT, I HAVE NO IDEA AS TO WHAT THE | | | SCOPE OF WORK IS TO BE UNDER THIS PERMIT. SUBMIT TWO | | | COPIES OF PLANS AND SPECIFICATIONS THAT CLEARLY | | | REFLECTS THE ENTIRE SCOPE OF WORK TO BE DONE. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 4) SHOW THE CORRECT BTU LOAD OF THE GRILL ON THE FLOOR | | | PLAN AND THE GAS RISER.WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | NOTE - I SUGGEST CONTACTING THIS RREVIEWER TO DISCUSS | | | THESE REVIEW COMMENTS SO I CAN ASSIST IN GETTING THIS | | | PERMIT ISSUED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|