| 2018-06-27 20:17:18 | 06/27/2018 3RD GAS REVIEW**DENIED** |
| | |
| | YOU HAVE ANSWERED 1 OF 4 COMMENTS. IF THESE PLANS ARE |
| | DENIED AGAIN A 4X PLAN REVIEW FEE WILL BE APPLIED. FL |
| | ST. STAUTE 553.80 (2B). |
| | |
| | 1) THE NEW BBQ ARTISAN GRILL DOCUMENTS PROVIDED DOES |
| | NOT SHOW IF COMPLIES WITH ANY SPECFIC CODE. YOUR |
| | PROVIDE DOCS LIST 2 MODELS 36" AND 32". WHICH ONE? THIS |
| | IS NOT THE BBQ THAT IS APPROVED UNDER THE MASTER |
| | #17070628. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 (2ND |
| | REQUEST) |
| | |
| | 2) THE VALUE OF THE APPROVED BBQ WAS $2,700.00 UNDER |
| | PERMIT # 17070628.PROVIDE THE COST OF THIS BBQ GRILL. |
| | THE VALUE OF THIS APPLICATION MUST BE CHANGED TO |
| | INCLUDE THE COST DIFFERANCE IN EQUIPMENT. WPB AMEND TO |
| | THE FBC 109.3. THE DIFFERENCE IN VALUE MUST BE APPLIED |
| | TO THIS PERMIT OR A REVISION UNDER PERMIT # 17070628 . |
| | |
| | 3) A HOOD VENT IS REQUIRED AS THIS BBQ GRILL WILL BE |
| | LOCATED UNDER A COVERED ROOF. THE FACT THAT IT HAS OPEN |
| | SIDE DOES NOT COMPLY. THE MASTER PERMIT #17070628 DOES |
| | NOT INCLUDE THE REQUIRED HOOD VENT IF BEING INSTALLED |
| | UNDER A COVERED OPENING. YOU HAVE NOT INCLUDE THIS |
| | INFORMATION IN YOUR APPLICATION EITHER. WHO WILL BE |
| | INSTALLING THE HOOD VENT? FBC-FUEL GAS SECTION 623. A |
| | SEPERATE MECHANICAL APPLICATION FOR PERMIT WILL BE |
| | REQUIRED.FBC 105.1 |
| | |
| | |
| | |
| | PLEASE BE ADVISED IF YOU ARE TO RESUBMIT ANY DRAWINGS |
| | THAT HAS A DESIGN PROFESSIONAL NAME AND TITLE BLOCK IT |
| | IS REQUIRED UNDER FL . ADMIN CODE 61G15-23.001( |
| | ENGINEERS) OR 61G1-16.001 (ARCH). |
| | |
| | PLEASE CONTACT FPU TO VERIFY THE SIZE OF THE GAS METER |
| | CAN HANDLE THE REQUIRED BTU'S |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |
| | [email protected] |
| | |
| | |