| 2018-01-22 05:39:05 | 01/22/2018 GAS 1ST REVIEW**DENIED** |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1) CITY RECORDS SHOW THE TOTAL EXISTING LOAD ON THE GAS |
| | SYSTEM AS 1,410,000 BTU. PLEASE PROVIDE AN ACCURATE |
| | ISOMETRIC DRAWING AND VERIFY THAT THE SYSTEM IS NOT |
| | UNDERSIZED @ .5LB. FBC 107.2.14.LIST THE BTU LOAD OF |
| | EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | REFER TO THE 2014 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 |
| | AND TABLES 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. |
| | SEC. G2413 |
| | |
| | 2) CITY RECORDS SHOWS THAT THE EXISTING GAS SYTEM WAS |
| | SIZED BASED ON 402.2 (2) USING A PRESSURE DROP OF .5. |
| | PLEASE RESUBMIT USING THE SAME TABLE AS EXISTING. FBC |
| | 107.2.1. ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING |
| | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN |
| | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 |
| | FBC-FUEL GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. |
| | G2412.4, G2412.8, G2413.1, G2413.2, & G2413 |
| | |
| | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL NEW GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | 561-805-6695 |